cnReach N500 User Guide
System Configuration
phn-4673_003v000 (November 2018)
2-44
To create a new Modbus TCP to RTU bridge connection:
1.
In the UI, go to
Serial
>
Modbus Bridging.
2.
Click
Add
to display the bridging settings.
3.
Click the
Mode
list and select
TCP Server
or
TCP Client
for each part of the bridge connection. Typically,
the TCP Bridge Connection is in TCP Server mode and the RTU Bridge Connection is in TCP Client mode. The
Host Address
field is enabled for TCP Clients only.
4.
In
Port#
, enter the port number for the bridge. This is the port through which the bridge communicates.
5.
For the TCP Client, enter the host IP address in
Host Address
. (You can automatically select the local host by
clicking localhost.)
6.
Click
Commit
to save the changes.
The following diagram shows configuration of a Modbus TCP/Modbus RTU service and their related
logical components.
Please notice that Modbus TCP/Modbus RTU conversion can also be sent over seamless serial, because once Modbus TCP is
converted to Modbus RTU, it can be processed like regular serial traffic. The following shows an example on how to do it.
Содержание cnReach N500
Страница 1: ...User Guide cnReach N500 System Release 01 30 900 MHz 700 MHz 450 MHz 220 MHz ...
Страница 17: ...Chapter 1 Product Description cnReach N500 Radio Module ...
Страница 70: ...cnReach N500 User Guide System Configuration phn 4673_003v000 November 2018 2 38 ...
Страница 77: ...cnReach N500 User Guide System Configuration phn 4673_003v000 November 2018 2 45 ...
Страница 82: ...cnReach N500 User Guide System Configuration phn 4673_003v000 November 2018 2 50 ...
Страница 117: ...cnReach N500 User Guide Technical Reference phn 4673_002v000 March 2018 3 5 ...
Страница 122: ...cnReach N500 User Guide Technical Reference phn 4673_002v000 March 2018 3 10 ...
Страница 148: ...cnReach N500 User Guide Technical Reference phn 4673_002v000 March 2018 3 36 ...
Страница 155: ...cnReach N500 User Guide Technical Reference phn 4673_002v000 March 2018 3 43 ...