Calumet GSA Скачать руководство пользователя страница 23

GSA

 

Gas-Fired Steam Boilers – 

Boiler Manual

23

Part Number 550-110-738/0703

Check/test. . . . . . . . . .

Boiler relief valve

1. After following the warning directions below, if the relief valve

weeps or will not seat properly, replace the relief valve.

Before testing, make certain discharge pipe is properly
connected to valve outlet and arranged to contain
and safely dispose of boiler discharge. Wear gloves
to protect your hands from hot surfaces. Verify that
discharge piping is installed in accordance with this
manual and the instructions on the relief valve tag.
Failure to comply will expose operator and others to
severe personal injury or death.
Safety relief valves should be reinspected AT LEAST
ONCE EVERY THREE YEARS, by a licensed
plumbing contractor or authorized inspection agency,
to ensure that the product has not been affected by
corrosive water conditions and to ensure that the
valve and discharge line have not been altered or
tampered with illegally. Certain naturally occurring
conditions may corrode the valve or its components
over time, rendering the valve inoperative. Such
conditions are not detectable unless the valve and
its components are physically removed and
inspected. This inspection must only be conducted
by a  plumbing contractor or authorized inspection
agency — not by the owner. Failure to reinspect the
boiler relief valve as directed could result in unsafe
pressure buildup, which can result in severe personal
injury, death or substantial property damage.
Check the setting of the boiler limit control. The control
should never be set with a pressure above 10 psig.
Operating at a higher pressure can cause damage
to the boiler relief valve.
The boiler relief valve must be tested at least monthly
during the heating season to verify the valve and
discharge piping flow freely. If corrosion and/or
deposits are noticed within the valve body, testing
must be performed more often. A “try lever test” must
also be performed at the end of any non-service
period. Follow the instructions below for a “try lever
test”:

• With the system at operating pressure, lift and hold

the test lever fully open for at least 5 seconds to flush
the valve seat free of sediment and debris. Then
release lever and permit the valve to snap shut.

Review with owner

1. Review the User’s Information Manual with the owner.

2. Emphasize the need to perform the maintenance schedule

specified in the User’s Information Manual (and in this manual
as well).

3. Remind the owner of the need to call in a licensed contractor

should the boiler or system exhibit any unusual behavior.

4. Remind the owner to follow the proper shutdown procedure

and to schedule an annual start-up at the beginning of the next
heating season.

The boiler contains ceramic fiber and fiberglass
materials. Use care when handling these materials
per instructions on page 32 of this manual. Failure to
comply could result in severe personal injury.

1. Shut down boiler — Follow “To Turn Off Gas to Appliance”

instructions on boiler and 

“Lighting Instructions”.

2. Disconnect breeching and remove damper and draft diverter.

3. Remove upper rear jacket panel. Turn back jacket insulation to

expose collector hood.

4. Remove collector hood. Clean excess boiler cement from

collector hood and cast iron sections.

5. Remove burners from base of boiler. Follow “Burners and base”

on page 21, to thoroughly clean burners. Place newspaper in
base of boiler to collect soot that will fall.

6. With a wire flue brush, clean between the sections.

7. Remove paper and soot. Vacuum or brush base and

surrounding area.

8. Replace collector hood. Seal with boiler cement.

Cleaning boiler heating surfaces

11 Service and maintenance 

continued

Содержание GSA

Страница 1: ...ersonal injury or property damage Special instructions on installation operation or maintenance that are important but not related to personal injury or property damage INSTALLER Read all instructions...

Страница 2: ...ubstantial property damage When servicing boiler 1 To avoid electric shock disconnect electrical supply before performing maintenance 2 To avoid severe burns allow boiler to cool before performing mai...

Страница 3: ...e room must provide the following minimum clearances in all directions to the boiler and components Jacket and flue collector sides rear 6 inches Jacket front 18 inches Vent pipe other than Type B ven...

Страница 4: ...ons will occur causing severe personal injury or death Inspect existing chimney before installing boiler Failure to clean or replace perforated pipe or tile lining will cause severe personal injury or...

Страница 5: ...detergents and cleaning solvents found in household laundry rooms Adhesives used to fasten building products and other similar products Areas likely to have contaminants Dry cleaning laundry areas and...

Страница 6: ...cation continued Exhaust fans and air movers The appliance space must never be under a negative pressure Always provide air openings sized not only to the dimensions required for the firing rate of al...

Страница 7: ...upward at least per lineal foot toward chimney or vent and support with hangers to prevent sagging 4 Breeching must not be connected to any portion of a mechanical draft system that can operate under...

Страница 8: ...th 3 8 diameter hole in vent damper hole Minimum clearances Provide a minimum of 6 between the vent damper and any combustible material See Minimum clearance to combustible materials page 3 for minimu...

Страница 9: ...3 3 1 Note 24 minimum from waterline to header Figure 5 Recommended piping piping for parallel flow systems only Connecting to counterflow piping Apply the recommended piping in Figures 4 through 7 on...

Страница 10: ...arge amounts of steam and or hot water Therefore to reduce the potential for bodily injury and property damage a discharge line MUST be installed that Is connected from the outlet to a safe point of d...

Страница 11: ...ar floor close to floor drain to eliminate potential of severe burns Do not plug valve or place any obstruction in blowdown line 3 Water feeders are not recommended for primary control A low water cut...

Страница 12: ...n cap and tee b Install ground joint union for servicing when required c Install manual shutoff valve in gas supply piping outside boiler jacket when required by local codes or utility requirements d...

Страница 13: ...Code Part 1 and any local codes Figure 11 Field wiring connections service switch and thermostat or end switch provided by installer 6 Field wiring Wiring connections Boiler is shipped with controls...

Страница 14: ...ease Failure to properly clean can result in violent fluctuations of water level water passing into steam mains or high maintenance costs on strainers traps and vents Do not use petroleum based cleani...

Страница 15: ...ning or sealing compounds in boiler system Severe damage to boiler will occur resulting in substantial property damage 1 Check system piping for leaks If found shut down boiler and repair immediately...

Страница 16: ...installed controls If boiler has an additional high limit low water cutoff or other controls test for operation as outlined by manufacturer Burners should be operating and should go off when controls...

Страница 17: ...ighted following the Lighting Instructions in this manual and on boiler Vent damper will remain closed until a call for heat 2 Call for heat When thermostat circuit closes the boiler vent damper is en...

Страница 18: ...the appliance 5 When equipped with Johnson Controls vent damper Model M35 manually rotate damper blade in direction of arrow to Open position indicated on damper assembly 6 Turn gas control knob clock...

Страница 19: ...nspect the appliance and to replace any part of the control system and any gas control which has been under water 1 Stop Read the safety information above on this label 2 Set the thermostat to lowest...

Страница 20: ...Service and maintenance Service technician see following pages for instructions Owner maintenance see User s Information Manual for instructions A NNNUAL START UP Inspect Reported problems Boiler area...

Страница 21: ...Piping 1 Check the boiler interior piping and all system piping for signs of leaks 2 Repair any leaks before proceeding Do not use petroleum based cleaning or sealing compounds in boiler system Severe...

Страница 22: ...per on page 15 2 Check gas piping per pages 12 and 14 verifying no indications of leakage and all piping and connections are in good condition 3 Read the Lighting Instructions page 18 or 19 whichever...

Страница 23: ...the heating season to verify the valve and discharge piping flow freely If corrosion and or deposits are noticed within the valve body testing must be performed more often A try lever test must also...

Страница 24: ...ns pages 18 and 19 If gas is available and you cannot obtain a pilot flame try purging the gas line and cleaning pilot and pilot gas tubing Follow Lighting Instructions again If you still cannot obtai...

Страница 25: ...to closed position Close thermostat contacts Vent damper will rotate to open position Is 24VAC present across gas valve terminals Remove damper harness from damper harness plug TEMPORARILY install jum...

Страница 26: ...n assembly flue collector draft diverter vent damper and base assembly 13 Replacement parts The boiler contains ceramic fiber and fiberglass materials Use care when handling these materials per instru...

Страница 27: ...738 0703 Figure 17 Jacket assembly 13 Replacement parts continued The boiler contains ceramic fiber and fiberglass materials Use care when handling these materials per instructions on page 32 of this...

Страница 28: ...GSA Gas Fired Steam Boilers Boiler Manual 28 Part Number 550 110 738 0703 Figure 18 Controls and trim 13 Replacement parts continued...

Страница 29: ...GSA Gas Fired Steam Boilers Boiler Manual 29 Part Number 550 110 738 0703 13 Replacement parts continued Figure 19 Gas controls...

Страница 30: ...Gas connection manifold size Note 2 inches NPT V Damper height inches D Vent diameter inches W Jacket width inches Approximate shipping weight GSA 075 3 2 1 2 6 5 17 430 GSA 100 3 2 1 2 6 5 17 430 GSA...

Страница 31: ...nts of the building and nothing need be added for normal piping and pickup Ratings are based on a piping and pickup allowance of 1 333 An additional allowance should be made for unusual piping and pic...

Страница 32: ...or base insulation from the boiler and place it in a plastic bag for disposal Wash potentially contaminated clothes separately from other clothing Rinse clothes washer thoroughly NIOSH stated First Ai...

Отзывы: