All 240V spas must be permanently connected (hard
wired) to the power supply. See the wiring diagram
on page 7.
These instructions describe the only acceptable
electrical wiring procedure . Spas wired in any
other way will void your warranty and may
result in serious injury .
When installed in the United States, the electrical
wiring of this spa must meet the requirements of
NEC 70 and any applicable local, state, and federal
codes.
The electrical circuit must be installed by an
electrical contractor and approved by a local
building or electrical inspector .
Failure to comply with state and local codes
may result in fire or personal injury and will be
the sole responsibility of the spa owner .
The power supplied to the spa must be on a dedicated
GFCI protected circuit as required by NEC 70 with no
other appliances or lights sharing the power.
Use copper wire with THHN insulation. Do not use
aluminum wire.
Use the table below and on the next page to determine
your GFCI and wiring requirements.
Wire runs over 85 feet must increase wire gauge
to the next lower number. For example: A normal
50 amp GFCI with four #6 AWG copper wires run
over 85 feet would require you to go to four #4 AWG
copper wires.
240 Volt Electrical Installation
GFCI and Wiring Requirements
Single voltage systems (except Ultimate Fitness -- see next page)
Control System
GFCI Required
Wires Required
VS300
One 40 amp GFCI
Four #8 AWG copper wires
9800 (except Ultimate Fitness spas - see next page)
One 50 amp GFCI
Four #6 AWG copper wires
VS513Z
One 50 amp GFCI
Four #6 AWG copper wires
BP2000
One 60 amp GFCI
Four #6 AWG copper wires
Dual voltage system
The 5100DV control system is set at the factory to run on the low power setting for 40 amp operation. This is
the default setting. Spa owners can have their installer change this setting so the spa will run on high power
for 50 amp operation.
See configuration instructions on
page 8.
Warning: Never set a spa to run on high power without installing a properly rated GFCI .
Control
System
Default
setting
Power Setting
GFCI Required
Wires Required
5100DV
Power saver mode
Factory default
One 40 amp GFCI
Four #8 AWG copper wires
High power setting
See configuration
instructions on page 8.
One 50 amp GFCI
Four #6 AWG copper wires