- 20 -
6.16
Function list & explanation
The functions are contained within an initial display and 3 menus:-
Setting menu
(pass code protected) see Section 6.18.
Advanced setting menu
(pass code protected) see Section 6.19.
Test menu
(pass code protected) see Section 6.20.
6.17
Initial display
On start up, and during operation, if the unit has had no button inputs for
1 minute, a home screen (see Section 7.11) will be displayed with system
pressure, tank water level, any active alarm and any pump that is operating at
the
time.
By using buttons A & C to scroll up or down the following screens will be
displayed:-
System
pressure
Active
errors
System fill status
Pump
activity
Pump run time
Alarm
reset
6.18
Setting menu
(Pass code protected, if set)
The following functions can be set and modified:-
System pressure (2)
see Fig. 20
Sets the required system pressure.
Set in 0.1 bar
increments up to the maximum set value for the model.
Unimat-E35 & Duromat-E35, 3.5 bar max.,
Unimat-E50 & Duromat-E50, 4.1 bar max.
Differential pressure (3)
see Fig. 20
Sets the pressure the unit will turn on at as the
system pressure falls. Relative to the system
pressure.
Set in 0.05 bar increments below the System pressure
(2), cannot be set above 0.1 bar below the System pressure (2).
Hi Alarm (1)
see Fig. 20
Sets high system pressure alarm.
Set in 0.05 bar
increments above the System pressure (2). Cannot be set below
System pr 0.05 bar. Alarm auto resets when system
pressure is reduced below alarm level.
Lo Alarm (4)
see Fig. 20
Sets low system pressure alarm.
Set in 0.05 bar
increments below the System pressure (2) - Differential pressure (3)
- 0.05 bar. Alarm auto resets when system pressure is increased
above alarm level
System fill
Turns on system fill option
. System fill option will turn off
once the System pressure (2) has been reached or a period of
24 hours has passed since it was set to ‘on’. Lo alarm and Max
runtime functions are disabled whilst System fill is turned on.
Pumps will stop if the System pressure (2) or Hi alarm pressure (1)
is reached.
Start Activity High
Alarm triggered if the unit starts more than the
preset limit in 24 Hours.
Set to minimum of 100 starts per 24 hrs. Set in increments of 100.