Page 22
HEAT PUMPS FOR OUTDOOR POOLS
REVERSE CYCLE DEFROST (ALY, BLY)
MODEL
Units
AW631
AW831
AW1231
AW1531
HEAT TO POOL WATER
AMBIENT 10°C, WATER 24°C :-
kWhr
7.2
9.9
12.4
17.7
ELECTRICAL
ELECTRICAL SUPPLY 1 PHASE
ELECTRICAL SUPPLY 3 PHASE
TOTAL POWER CONSUMED:-
AMBIENT 10°C, WATER 24°C :-
kWhr
1.8
2.3
3.1
4.2
AMBIENT 20°C, WATER 24°C :-
kWhr
2.0
2.5
3.3
4.3
MIN SUPPLY CAPACITY (Max F.L.A.) 1 ph N:-
amps
14.3
17.4
19.0
N/A
MIN SUPPLY CAPACITY (Max F.L.A.) 3 ph N:-
amps
6.0
6.2
8.0
13.0
MAX' SUPPLY FUSE 1 ph N:-
amps
20.0
25.0
30.0
N/A
MAX' SUPPLY FUSE 3 ph N:-
amps
10.0
10.0
15.0
18.0
WATER FLOWS ETC
POOL WATER FLOW RATE:-
litres/min
115
115
160
160
POOL WATER PRESSURE DROP (@ Rated Flow):-
metres hd
1.0
1.0
2.0
2.0
MAX WORKING PRESSURE POOL WATER:-
bar
3.5
3.5
3.5
3.5
POOL WATER CONNECTIONS:-
inches
1 1/2" BSPM
1 1/2" BSPM
1 1/2" BSPM
1 1/2" BSPM
CONDENSATE DRAIN CONNECTIONS:-
inches
3/4" BSPM STUD 3/4" BSPM STUD 3/4" BSPM STUD 3/4" BSPM STUD
COMPRESSOR
NOMINAL POWER CONSUMED:-
kWhr
1.8
2.14
2.6
3.8
LRA.- 1 ph N:-
amps
66
63
100
N/A
RLA:- 1 ph N:-
amps
11.4
14
16.6
N/A
SOFT START AMPS 1 ph N:-
amps
29
31
35
N/A
LRA:- 3ph N:-
amps
32
30
48
48
RLA: -3 ph N:-
amps
4
4.65
7.3
10
SOFT START AMPS 3 ph N:-
amps
14
14
17
25
MAlN FAN
AIR FLOW (Anemometer @ air on grille. Wet evaporator):-
m³/hr
1800
2700
3000
4700
MAX EXTERNAL STATIC PRESSURE :-
mm Wg
0
0
0
0
FLA:- 1 ph N:-
amps
0.7
0.7
0.97
2
GENERAL DATA
HERMETIC SYSTEM
GAS CHARGE R407c
kg
2.31
3.0
4.5
4.5
PHYSICAL DIMENSIONS
WIDTH (Un-packed):-
mm
1076
1076
1076
1200
DEPTH (Un-packed):-
mm
485
485
485
485
HEIGHT (Un-packed):-
mm
1255
1255
1355
1355
WEIGHT (Un-packed) :-
kg
133
142
157
170
230V/~1N/50Hz
400V/~3N/50Hz
For Accurate Application Sizing Consult CALOREX Heat Pumps Ltd.
NOTES:
1) Weight and dimensions nett
2) Performance design Iimitations
Ambient = -15°C min, 35°C max
Water = 10°C min, 40°C max
3) Pool water to have correct balance, pH 7.4 ± 0.4 Free Chlorine 1.0 - 3.0 ppm
4) Allow 500mm clearance to service panels
5) Calorex reserve the right to change or modify models without prior notice.
6) R407c Global Warming Potential (GWP) 1700.
1mm WG = 9.8 Pa
1m hd = 1.4 psi
1L/min = 0.22 gall/min