Page 23
SD092750 ISSUE 34
AIR/WATER VARIHEAT HEAT PUMPS FOR INDOOR POOLS
DEHUMIDIFICATION WITH HEAT RECOVERY TO WATER AND
AIR (METRIC SPECIFICATIONS) (50Hz MACHINES)
Datasheet
MODEL:-
Units
550
800
1200
1400
1800
4000
DEHUMIDIFICATION DUTY
litres/hr
3·8
6·1
8·3
10·0
12·4
26·8
HEAT TO AIR
VIA HEAT PUMP (MODE A):-
kW
1·6
2·3
3·0
1·5
2·5
8·0
VIA HEAT PUMP (MODE B):-
kW
3·0
3·5
5·2
5·0
8·5
20·0
HEAT TO WATER
VIA HEAT PUMP (MODE A):-
kW
4·0
5·5
7·0
10·0
12·0
26·0
VIA HEAT PUMP (MODE B):-
kW
2·8
3·0
3·0
4·2
5·0
12·0
Flow Rate Pool Water max
L/min
100
100
120
35
35
95
Flow Rate Pool Water min
L/min
80
80
100
30
30
90
Pressure Drop @ Rated Flow max
M/hd
1·4
1·4
1·4
2·5
2·5
3·4
Pressure Drop @ Rated Flow min
M/hd
1·2
1·2
1·2
1·8
1·8
3·1
Water connections
inches
1½ BSPF
1½ BSPF
1½ BSPF
1½ BSPM 1½ BSPM 1½ BSPM
Condensate drain connections
inches
¾
¾
¾
¾ BSPM
¾ BSPM
1½ BSPM
domestic
w aste
domestic
w aste
domestic
w aste
ELECTRICAL
TOTAL POWER CONSUMED (STD FAN)
kW
1·8
2·5
4.14
4·0
5·0
10·0
TOTAL POWER CONSUMED ('F' FAN)
kW
2·2
2·9
4·0
4·2
5·2
10.4
MAX RUNNING AMPS ( STD FAN) 1 ph N:-
amps
12·8
17.2
24
N/A
N/A
N/A
MAX RUNNING AMPS ('F' FAN) 1 ph N:-
amps
13·9
20.6
24.7
N/A
N/A
N/A
MAX RUNNING AMPS ( STD FAN) 3 ph N:-
amps
5·8
8
14
8·8
10.5
27.32
MAX RUNNING AMPS ('F' FAN) 3 ph N:-
amps
9.7
11.3
14.5
9
10.6
27.82
MAX' SUPPLY FUSE STD 1 ph N:-
amps
15
25
35
N/A
N/A
N/A
MAX' SUPPLY FUSE 'F' 1 ph N:-
amps
20
32
35
N/A
N/A
N/A
MAX' SUPPLY FUSE STD 3 ph N:-
amps
10
13
20
15
16
40
MAX' SUPPLY FUSE 'F' 3 ph N:-
amps
16
16
20
15
16
40
STARTING CURRENT STD MODEL 1ph
amps
42
76
103
N/A
N/A
N/A
STARTING CURRENT SOFT START (S) MODEL 1ph
amps
23
31
34
N/A
N/A
N/A
STARTING CURRENT STD MODEL 3ph
amps
30
42
48
45
76
167
STARTING CURRENT SOFT START (S) MODEL 3ph
amps
19
23
25
24
31
39
FAN
AIR FLOW (anemometer @ air on, w et evaporator)
m³/hr
1800
2500
3000
3500
4300
9000
MAX EXTERNAL STATIC PRESSURE STD
mm Wg
5
6
6
4
4
8
MAX EXTERNAL STATIC PRESSURE 'F' MODEL
mm Wg
23
22
16
16
14
16
NOISE LEVEL @ 3M
dbA
58
58
60
60
60
63
GENERAL DATA
HERMETIC SYSTEM
GAS CHARGE R407c
kg
1·81
2·04
2·5
6·8
7·25
14·5
DIMENSIONS :-
Width (un-packed)
mm
660
660
810
980
980
1730
Depth (un-packed)
mm
660
660
660
700
700
1250
Height (un-packed)
mm
1313
1313
1313
1490
1490
1600
WEIGHT approx' (Un-packed):-
kg
120
130
170
210
230
49
NOTES
(1) Performance data based on pool hall air @ 28ºC, 60% RH, Water @ 26ºC.
1mm WG = 9·8 Pa
(2) Operation Mode ‘A’. Pool water temperature not satisfied.
1 m hd = 1·4 psi
Operation Mode ‘B’. Pool water temperature satisfied.
1 l/hr = 2·2 lbs/hr
(3) Weight and Dimensions Nett.
(4) Allow 500mm clearance to service panels
(5) Min. Pool Hall air temperature 20ºC
(6) Pool water to have correct balance pH 7·4 ± 0·4. Free Chlorine 1·0 - 3·0 ppm.
(7) Calorex reserve the right to change or modify models without prior notice.
(8) R407c Global Warming Potential (GWP) 1700.