![Calix ODC-80 Скачать руководство пользователя страница 20](http://html1.mh-extra.com/html/calix/odc-80/odc-80_installation-manual_3459610020.webp)
14
Calix ODC-80 Installation Guide
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2001-2003 Calix. All Rights Reserved.
Cable requirements
Recommended ground cable requirements
•
Use AWG #2 cable (AWG #6 minimum).
•
Use a 2-hole compression lug with hole spacing of 5/8", 1", or 1-1/4", and a bolt
size of 1/4".
•
Leave 4 feet of cable above the top of the pad.
Recommended AC power cable requirements
•
Use AWG #6 cable minimum.
•
Leave 6 feet of cable above the top of the pad.
•
Follow National Electric Code (NEC) and local codes when installing AC power.
Recommended copper subscriber cable requirements
•
Leave 8 to 10 feet of cable above the top of the pad.
•
Have appropriate termination equipment and tools available.
Recommended fiber cable requirements
•
Use single-mode fiber only.
•
Use a fiber splice value no greater than 0.5 dB loss.
•
Leave 6 feet of cable above the top of the pad.
Note
Modify for local conditions
Local climatic conditions, site conditions, or local practices may
require modifications to cable termination. The following are
minimum requirements.
Содержание ODC-80
Страница 1: ...Calix ODC 80 Installation Guide July 2003 Part 220 00029 Rev 11 ...
Страница 2: ......
Страница 6: ......
Страница 7: ...1 Chapter Before You Begin Installing the ODC 80 ...
Страница 8: ......
Страница 23: ...2 Chapter Placing the ODC 80 on a Pad ...
Страница 24: ......
Страница 30: ......
Страница 31: ...3 Chapter Installing Power Subscriber Cables and Equipment ...
Страница 32: ......
Страница 74: ......
Страница 75: ...4 Chapter Maintaining and Troubleshooting the ODC 80 ...
Страница 76: ......
Страница 80: ......
Страница 92: ......
Страница 103: ...5 Chapter Reference ...
Страница 104: ......
Страница 106: ......