background image

 

 

Proprietary Information: Not for use or disclosure except by written agreement with Calix. 

© 2001-2007 Calix. All Rights Reserved. 

Introduction 

This document details the National Electrical Code (NEC) requirements for properly 
grounding an ONT during installation. 

This document also provides specific information for installing the ground on the Calix 500-
Series or 700-Series ONTs, on the following models: 

ONT Type

Models Available

500-Series 

410, 412, 422, 424, 502, 504, 522, 524, 560 

700-Series 

710, 711, 712, 714, 720, 721, 722, 724, 740, 761  

 

Grounding Purpose 

Providing proper grounding to the ONT has two different purposes: 

y

 

Grounding provides for the safety of the intended user and maintenance personnel. The 
grounding requirements of the NEC provide a degree of safety in the event the outer 
metallic case of the protected device becomes energized by a current-carrying conductor. 
In this event, the grounded case would cause the over-current device to trip, thereby 
removing the power to the device. 

y

 

The protection and survivability of the electronics equipment. High voltage spikes that 
occur during electrical storms, as well as static buildup on power utility lines, have been 
known to cause a great deal of damage to electronic equipment. When the voltage 
potentials reach sufficient amplitude, flashovers take place. In most cases, damage is 
caused by the super heating present during the flashover. The high voltage potentials that 
are induced into AC utility conductors and communications cables during electrical 
storms are of a wavelength that approaches the RF spectrum. To be effective in the 
discharging of induced RF energy, grounding conductors must provide a low impedance 
path to earth. Keeping conductors as short as possible and using the most direct path, 
free of sharp bends, will help to lower the impedance of the ground circuit.  

Note: 

Grounding conductors must never be placed inside a metallic conduit unless bonded 

at both ends of the conduit so that the conduit itself becomes the conductor. 

 

 

Содержание 500 Series

Страница 1: ...Calix ONT Grounding Implementation January 2007 220 00178 Rev 10...

Страница 2: ......

Страница 3: ...Not for use or disclosure except by written agreement with Calix 2001 2007 Calix All Rights Reserved Contents Introduction 5 Grounding Purpose 5 NEC and Grounding 6 Testing the Earth Electrode 7 Full...

Страница 4: ...4 Proprietary Information Not for use or disclosure except by written agreement with Calix 2001 2007 Calix All Rights Reserved...

Страница 5: ...case would cause the over current device to trip thereby removing the power to the device y The protection and survivability of the electronics equipment High voltage spikes that occur during electric...

Страница 6: ...The earth electrode can be a metallic cold water pipe or a copper clad steel rod that has been driven into the ground to a depth of at least 8 feet Metallic cold water pipes that run under ground for...

Страница 7: ...depends on the chemical makeup and ambient moisture content of the soil The testing of an electrode measures the effectiveness of the earth electrode to provide electrical contact with the earth The...

Страница 8: ...re measurements are taken beyond this point the amount of resistance to earth will start to increase again The test setup as illustrated below uses an Earth Resistance Megger to determine the resistan...

Страница 9: ...ectrode being tested and the outer current electrode may be limited by the physical characteristic of the surrounding area or the length of the test conductor being used It is not uncommon for the out...

Страница 10: ...should be kept for each ONT installation In some locations extremely high earth ground resistance is present In these locations chemicals that lower earth resistance can be added to the earth that sur...

Отзывы: