Installation: 

 

To install the flow switch correctly follow these instructions: 

 

-  When selecting the blade, identify the diameter of  the  

pipe to which the appliance will be fitted;
 -  The appliance comes pre-fitted with the 1” blade;
 -  For  diameters  of 1 1/4” (DN 32)  and above, the  pre-
fitted  blade  should be removed and  the l ong  blade  
fitted, cutting it  to the  correct  corresponding  size  for  
the  desired  diameter;
 -  Fit the  flow  switch  to  the  pipe,  carefully  observing  
the  direction of  flow indicated  by  the  arrows  stamped  
on  the cover and  on  the  switch  mounting  plate.  When  
fitted,  the  distance  between  the  upper  surface  of  the  
pipe  and  upper  surface  of  the  switch  mounting  plate  
should  be  3 1/8” (80 mm);
 - The  tee  connection in  the  pipe  can  be  formed  by  
the  direct welding of a threaded socket;
 - This  also  applies  to  a  1” (DN 25)  diameter  pipe,  
as  the  blades  are  designed  to  be contained in  these  
smaller  dimensions.
 -  It is  however  advisable  to  check  that  the  weld is  
free  from  burrs  on  the inside  so  that  the  blade  can  
move  freely in  the  the connection;
 -  Whenever possible the flow switch should be installed 
with control stem in the vertical position to avoid deposits  
of impurities which may cause it to function incorrectly.

4

Содержание Uni-Switch 626 Series

Страница 1: ...tainless steel is used in the construction of many key parts including the bellows which protects the switch from corrosion With a protection classi cation of NEMA type 3 IP54 the switch can be used i...

Страница 2: ...Teflon provides lubricity so that care must be exercised not to over tighten joints Failure to follow these instructions could result in property damage and or personal injury CAUTION Electrical shoc...

Страница 3: ...r lubrifiant Teflon permet de sorte qu il faut prendre soin de ne pas trop serrer les articulations Le non respect de ces instructions peut entra ner des dommages mat riels et ou des blessures ATTENTI...

Страница 4: ...on the cover and on the switch mounting plate When tted the distance between the upper surface of the pipe and upper surface of the switch mounting plate should be 3 1 8 80 mm The tee connection in th...

Страница 5: ...ded the common black wire and normallyopen red wire contacts are closed while the common black wire and the normally closed blue wire are open Diagrams showing the internal connections of the micro sw...

Страница 6: ...e calibration screw A i n a clockwise direction f or the contacts to close at higher ow rate values or in a counterclockwise direction for lower ow rate values When the adjustment has been made lock t...

Страница 7: ...Operating ow rates gpm lpm 7...

Страница 8: ...Caleffi North America Inc 3883 West Milwaukee Road Milwaukee WI 53208 T 414 238 2360 F 414 238 2366 8 NOTES 12 2022...

Отзывы: