Function

The  Caleffi  Series  626  water  flow  switch  detects  the  presence  
or  absence  of  flow  in  piping  of  heating,  air  conditioning,  cooling  
and  water  treatment  systems  as  well  as  in  pumping  and  process  
systems.  In  heating  systems,  the  flow  switch  is  normally  used  to  
shut  off  the  burner  of  the  boiler  whenever  there  is  no  circulation  
of  the  carrier  fluid  in  the  boiler  circuit.  A  lack  of  circulation  
can  damage  critical  components  and  impair  the  operation  of  
temperature  sensitive  safety  and  protection  devices. 
 This  item  is  designed  for  use  in  closed  hydronic  systems.  Do  not  
use  in  plumbing  applications.  This  item  does  not  meet  the  low-lead  
plumbing  standards of U.S. and Canada. 

General Characteristics 

A  stainless  steel  bellows  separates  the  electrical  and  hydronic  sections,  preventing  the  possibility  
of  contact  of  the  fluid  with  the  electrical  components.  Stainless  steel  is  used  in  the  construction  
of  many  key  parts, including the bellows, which protects the switch from corrosion. With  a  protection  
classification of NEMA type 3 (IP54), the  switch  can  be  used  in particularly  humid  and  dusty  
environments.  The  cover  is  made  of  a  special  non-combustible  plastic  material.  The  normally  open  
and  normally  closed  contacts  on  the  switch  enable  any  electrical  device  to  be  switched  on  or  off  
as  required at the operating flow rate. The operating point can be easily adjusted with the calibration screw. 

Technical Characteristics 

Connection size:       

Maximum operating pressure: 

Maximum temperature of the fluid: 

Minimum temperature of the fluid: 

Maximum ambient temperature:

Suitable for pipes: 

Electrical Data 

Max. Voltage: 

Max. Current: 

Electrical connection: 

Protection class: 

Certification Mark: 

1

” NPT male

150 psig (10 bar)

250° F (120° C)

-20° F  (-30° C) 

130° F (55° C)

1” to 8” (25 to 200mm)

 250 VAC 

 15A 

 ½” NPT threaded with strain relief

NEMA type 3 (IP54)

 Uni-Switch™ Universal Flow Switch 

 © Copyright 2022 Caleffi 

68235.07

www.caleffi.com

1

626 Series

Содержание Uni-Switch 626 Series

Страница 1: ...tainless steel is used in the construction of many key parts including the bellows which protects the switch from corrosion With a protection classi cation of NEMA type 3 IP54 the switch can be used i...

Страница 2: ...Teflon provides lubricity so that care must be exercised not to over tighten joints Failure to follow these instructions could result in property damage and or personal injury CAUTION Electrical shoc...

Страница 3: ...r lubrifiant Teflon permet de sorte qu il faut prendre soin de ne pas trop serrer les articulations Le non respect de ces instructions peut entra ner des dommages mat riels et ou des blessures ATTENTI...

Страница 4: ...on the cover and on the switch mounting plate When tted the distance between the upper surface of the pipe and upper surface of the switch mounting plate should be 3 1 8 80 mm The tee connection in th...

Страница 5: ...ded the common black wire and normallyopen red wire contacts are closed while the common black wire and the normally closed blue wire are open Diagrams showing the internal connections of the micro sw...

Страница 6: ...e calibration screw A i n a clockwise direction f or the contacts to close at higher ow rate values or in a counterclockwise direction for lower ow rate values When the adjustment has been made lock t...

Страница 7: ...Operating ow rates gpm lpm 7...

Страница 8: ...Caleffi North America Inc 3883 West Milwaukee Road Milwaukee WI 53208 T 414 238 2360 F 414 238 2366 8 NOTES 12 2022...

Отзывы: