background image

 68235.06 

 Installation: 

 To install the flow switch correctly follow these  instructions: 

 -   When   selecting   the   blade,   identify   the   diameter   of   the 
 pipe to which the appliance will be fitted; 
 - The appliance comes pre-fitted with the 1” blade; 
 -  For  diameters  of  1  1/4”  (DN  32)  and  above,  the  pre-fitted 
 blade  should  be  removed  and  the  long  blade  fitted,  cutting 
 it   to   the   correct   corresponding   size   for   the   desired 
 diameter; 

 -   Fit   the   flow   switch   to   the   pipe,   carefully   observing  the 
 direction   of   flow   indicated  by  the  arrows  stamped  on  the 
 cover   and   on  the  switch  mounting  plate.  When  fitted,  the 
 distance  between  the  upper  surface  of  the  pipe  and  upper 
 surface  of  the  switch  mounting  plate  should  be  3  1/8”  (80 
 mm); 

 -The   tee   connection   in   the   pipe   can   be   formed   by   the 
 direct welding of a threaded socket; 
 -This   also   applies   to   a   1”   (DN   25)   diameter   pipe,  as  the 
 blades   are   designed   to   be   contained   in   these   smaller 
 dimensions. 
 -It  is  however  advisable  to  check  that  the  weld  is  free  from 
 burrs  on  the  inside  so  that  the  blade  can  move  freely  in  the 
 tee connection; 
 -Whenever   possible   the   flow   switch   should   be   installed 
 with  control  stem  in  the  vertical  position  to  avoid  deposits 
 of impurities which may cause it to function incorrectly. 

 4 

Содержание Uni-Switch 626 Series

Страница 1: ...nic sections preventing the possibility of contact of the uid with the electrical components Stainless steel is used in the construction of many key parts including the bellows which protects the swit...

Страница 2: ...nnel trained in the proper application installation and maintenance of systems in accordance with all applicable codes and ordinances CAUTION Over tightening and breakage can occur with the use of Te...

Страница 3: ...bonne application installation et maintenance des syst mes conform ment aux codes et r glements locaux AVERTISSEMENT Un serrage excessif et une rupture peuvent survenir avec l utilisation de Te on com...

Страница 4: ...ped on the cover and on the switch mounting plate When tted the distance between the upper surface of the pipe and upper surface of the switch mounting plate should be 3 1 8 80 mm The tee connection i...

Страница 5: ...switch with Flow switch used to activate a device when ow stops When the decreasing operating ow is reached or stops the common black wire and the normally open red wire contacts open while the common...

Страница 6: ...the calibration screw A in a clockwise direction for the contacts to close at higher ow rate values or in a counterclockwise direction for lower ow rate values When the adjustment has been made lock...

Страница 7: ...68235 06 Operating ow rates gpm lpm 7...

Страница 8: ...68235 06 NOTES 06 2022 8...