background image

1

© Copyright 2020 Caleffi

Function

The ThermoSetter™ 1164 series adjustable thermal balancing 

valve is used for automatic balancing of recirculation loops in 

domestic hot water systems,  to speed hot water delivery, reduce 

water waste and save energy. The internal thermostatic balancing 

cartridge automatically modulates flow to ensure a constant 

temperature in the recirculation piping system. The 116 Series 

has an adjustment knob with 105°F to 150°F (40°C to 65°C) 

temperature scale indication. The adjustment knob is lockable for 

tamper-proofing. An integral dry-well holds a slide-in temperature 

gauge for local indication, or a sensor for remote temperature 

sensing. The optional check valve protects against circuit thermo-

syphoning.

ThermoSetter™ 

Recirculation Thermal Balancing Valve

H0006934.01

1164 Series

Installation, commissioning and servicing instructions

Product range

1164 series

    ThermoSetter, models w/ and w/o temperature  

 

gauge, w/ and w/o check valve.........................connections ½” and ¾” NPT female

www.caleffi.com

The valve is ICC-ES certified to NSF/ANSI 61 (180°F/82°C Commercial Hot) and NSF/ANSI 372, low 

lead laws. It meets codes IPC, IRC, UPC and NPC for use in accordance with the US and Canadian 

plumbing codes.

NSF 61

Technical specifications

Materials

 

Body:  DZR low-lead brass EN 12165 CW724R

Adjustable cartridge:                              PSU

Springs:                              Stainless  steel  EN  10270-3                                          

(AISI 302)

Hydraulic seals:            peroxide-cured EPDM

Adjustment knob:                                  ABS

Performance

Suitable fluid:                                         water 

Max. working pressure:          230 psi (16 bar)

Max. differential pressure:          15 psi (1 bar)

Adjustable temperature range: 

105–150°F (40 – 65°C)

Factory setting:                         135°F (58°C)

Max. inlet temperature:              195°F (90°C)

Cv (Kv) max:                                   2.1 (1.8)

Cv (Kv) min:                                  0.35 (0.3)

Cv (Kv) design:                              0.69 (0.6)

Certifications

1. Complies with codes IPC, IRC, UPC and 

NPC. 

2. ICC-ES certified to NSF/ANSI 61 

(180°F/82°C Commercial Hot), file          

PMG-1512.

3. NSF/ANSI 372, low lead certified by ICC-

ES, file PMG-1360.

Connections

Main connnections: 

½” NPT female

¾” NPT female

Temperature  gauge/probe  pocket:                                                       

 

Ø 10 mm metric

 

Temperature gauge code 116010

Scale:                            30 - 180°F (0–80°C)

Diameter:                                 1½” (40 mm)

Stem diameter:                         0.35” (9 mm)

Содержание ThermoSetter 1164 Series

Страница 1: ...uge w and w o check valve connections and NPT female www caleffi com The valve is ICC ES certified to NSF ANSI 61 180 F 82 C Commercial Hot and NSF ANSI 372 low lead laws It meets codes IPC IRC UPC and NPC for use in accordance with the US and Canadian plumbing codes NSF 61 Technical specifications Materials Body DZR low lead brass EN 12165 CW724R Adjustable cartridge PSU Springs Stainless steel E...

Страница 2: ...lubricity so that care must be exercised not to over tighten joints Failure to follow these instructions could result in property damage and or personal injury WARNING System fluids are under pressure or temperature can be hazardous Be sure the pressure has been reduced to zero and the system temperature is below 100 F 38 C Failure to follow these instructions could result in property damage and o...

Страница 3: ...a température peuvent être dangereux Être sûr que la pression a été réduite à zéro et la température du système est inférieure à 100 F 38 C Le non respect de ces instructions peut entraîner des dommages matériels et ou des blessures Le non respect de ces instructions peut entraîner des dommages matériels et ou des blessures ATTENTION Si le vanne d équilibrage Série ThermoSetter n est pas installé ...

Страница 4: ...130 140 180 150 160 170 Tset 2 1 0 35 Cvdesign 0 69 1 2 3 1 2 3 1 2 3 Thermostatic control 1164xxA series Thermostatic control with check valve 11614xAC series Installation Before installing the ThermoSetter flush the pipes to make sure that impurities in system will not interfere with valve performance Strainers of sufficient capacity at the inlet from the water main are highly recommended The Th...

Страница 5: ...loss calculations in the recirculation system follow traditional pipe sizing and head loss practices For pressurelosscalculations across the ThermoSetter valve use the design curve shown in the graph below This line represents a typical valve position under normal working conditions T 10 F Determinethepressure drop across the valve by selecting the branch design GPM on the graph X axis draw a vert...

Страница 6: ...it back on so that the internal groove couples with the protrusion on the knob holder nut When this block is used the reference of the indication of the temperature values on the knob is lost To restore it completely unscrew the lcoking screw Reposition the knob on MAX value Tighten the locking screw Maintenance The balancing adjustment cartridge can be removed from the valve body for periodic ins...

Страница 7: ...7 Application diagram 135 F 135 F 135 F 140 F 120 F NOTE Do not set at temperatures 120ºF if anti scald valves are not installed at the fixtures Hot water recirculation with thermal balancing valves ...

Страница 8: ...Caleffi North America Inc 3883 W Milwaukee Road Milwaukee WI 53208 T 414 238 2360 F 414 238 2366 3 20 2020 NOTES 8 ...

Отзывы: