4

Installation

The ThermoBloc™ boiler protection recirculation and distribution unit can be installed on both 
sides of the boiler following the flow directions indicated on the body. Installation is recommended 
on the return to the boiler in mixing mode, in vertical postion (axis of the pump horizontal and 
the axis of the thermostatic sensor vertical). This allows for the proper functionality of the natural 
circulation flapper check valve. Separately purchased ball valves (Caleffi code NA39753- 1” FNPT 
or NA39588- 1–1/4” 
FNPT) installed on 
each inlet and the 
mixed flow outlet are 
highly recommended 
for isolation and 
maintenance.

Natural circulation flapper check valve

The flapper check valve allows the natural thermosyphon circulation 

of the system heat transfer fluid when the pump stops running 

due to power failure. When the pump is running under normal 

conditions the thrust of the flowing medium keeps the flapper 

closed, forcing flow past the thermostatic sensor. When the pump 

stops running and the fluid in the boiler is at high temperature, 

natural circulation begins, by-passing the thermostatic sensor, 

preventing over heating in the boiler.

Flapper check valve – lock

Before installation, remove the screw that 

keeps the flapper check valve closed. 

This screw is factory-installed to prevent 

breakage during shipment. Removing the 

protective screw ensures full functionality 

of the flapper check valve as a natural 

circulation device. To do this, unscrew the 

union located on the mixed water outlet 

port (to boiler) and access the screw 

inside the valve body, unscrewing it using 

a phillips head screwdriver. 

BO IL ER

BO IL ER

Содержание ThermoBloc 281 Series

Страница 1: ...in an insulation shell These items are designed for use in closed hydronic systems Do not use in plumbing applications These items do not meet the low lead plumbing standards of U S and Canada Product range 281 series boiler protection recirculation and distribution unit NPT male or sweat sizes 1 1 1 4 Technical Characteristics Materials Body brass Shutter PSU Spring stainless steel Flapper check ...

Страница 2: ...n this manual to draw attention to safety related instructions When used the safety alert symbol means ATTENTION BECOME ALERT YOUR SAFETY IS INVOLVED FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN A SAFETY HAZARD Pump characteristics Insulation Material EPP Mean thickness 30 mm Density 45 kg m3 Working temperature range 40 210 F 5 100 C Thermal conductivity 0 037 W m K at 10 C Reaction to fire...

Страница 3: ...urn from the system port starts opening to produce the water mixing temperature in this phase the system loading begins When the mixed flow to the boiler temperature is greater than the set point of the boiler protection recirculation and distribution unit by approximately 18 F 10 C the bypass flow from the boiler port closes and water returns to the boiler at the same temperature as the return fl...

Страница 4: ...thermosyphon circulation of the system heat transfer fluid when the pump stops running due to power failure When the pump is running under normal conditions the thrust of the flowing medium keeps the flapper closed forcing flow past the thermostatic sensor When the pump stops running and the fluid in the boiler is at high temperature natural circulation begins by passing the thermostatic sensor pr...

Страница 5: ...or fig 2 4 Conduct appropriate maintenance or replace the thermostatic sensor with a new cartridge separately purchased The sensor can be fully inserted into the seat with a slight interference fit 5 Reassemble the shutter unit following the procedure in reverse order Replacement thermostatic sensor cartridges Easy replacement to change the ThermoBloc boiler protection recirculation and distributi...

Страница 6: ...Caleffi North America Inc 3883 W Milwaukee Road Milwaukee WI 53208 T 414 238 2360 F 414 238 2366 7 24 18 Installation Tip Scan to view 281 ThermoBloc TM Leave this manual for the user ...