background image

20

A

A

Periodic maintenance

Maintenance

All  maintenance  procedures  should  be  carried  out  by  an  authorised  technician.  Regular
maintenance  guarantees  better  efficiency  and  helps  to  save  energy.  Before  carrying  out  any
maintenance, repair or part replacement work, proceed as follows:
-   Cut off the electric supply
-   Remove the cover
-   Close the shut-off valves
-   Empty the heat interface unit using the drain cocks provided.

Exchanger replacement

-   As  a  preliminary  step,  remove  the  flow  sensor  (refer  to  “replacing  the  DHW  priority  flow

meter”, on page 21) and position it where it cannot be reached by any dripping liquid.

-   Remove the exchanger, loosening the 2 hex socket head screws fixing it in place (A)
-   Replace the exchanger and the O-rings.
-   Tighten  the  two  fixing  screws  (A)  after  having  checked  that  the  O-rings  are  correctly

positioned. Tightening torque 3-3,5 Nm.

N.B.

Make sure to respect the correct orientation of the plate heat exchanger when fitting it back.

OPERATIONS TO BE PERFORMED

Force an actuators reset by switching the HIU power supply OFF and then ON

Visually check for the absence of leaks and/or anomalies

Check for possible active errors shown on the user interface

Test correct operation of the pump by closing the thermostat contact or forcing it to close

Clean the strainers: on the primary flow line (component 17, page 4), on the secondary return line (19), upstream of the domestic water flow meter

(22)

After having isolated the HIU by means of shut-off valves, discharge the pressure in the secondary circuit and make sure the expansion vessel pre-

charge value is between 0.9 and 1.2 bar. Restore the pressure value, if necessary

Re-open the shut-off valves and restore secondary circuit pressure to a value between 1.3 and 1.7 bar

Check for the absence of any liquid dripping from the safety relief valve and ensure the drain is unobstructed

Check for the absence of internal leakage through the modulating valves when none of the services are active

Check correct setting of the set points (DHW and heating). Unless explicitly requested by the user or for normative reasons, a DHW temperature

set point of 50°C or lower is recommended

With the primary circuit at working temperature, check that the DHW flow rate at the correct temperature is sufficient

The following checks must be carried out at least once very 12 months, in accordance with the prescriptions of standard EN 806-5.

Summary of the technical parameters

Here follows a summary of the meaning and possible settings of the technical parameters:

Parameter

Meaning

Settings

t00

Temperature range of the HIU

0 = 45 - 75°C

1= 25 - 45°C

t01

Heating flow temperature control

0 = fixed set point

1 = fixed set point with RTL

2 = compensated on return temperature

3 = weather compensated

t02

DHW comfort mode

From 0 = pre-heating of the heat exchanger

1 = DHW recirculation

t03

Maximum % opening of the heating modulating valve

From 50 to 100

t04

Maximum % opening of the DHW modulating valve

From 50 to 100

t05

Configuration of the closing logic of the auxilliary microswitch

See page 16

t06

DHW temperature control

0 = fixed set point

1 = fixed set point with RTL

t07

Freezing of some settings

0 = All temperature settings can be modified

1 = Return temperature limits are freezed

t08

Anti-legionella

0 = disabled

1 = enabled between 3:00 to 3:30 a.m.

t09

Duration of a DHW recirculation cycle

1 unit = 10 seconds

Содержание SATK32 Series

Страница 1: ...de 10 Commissioning 9 Electrical installation 8 Hydraulic installation 5 Hydraulic components and diagram 4 Dimensions Technical specifications 3 Safety instructions 2 DHW function Comfort functions P...

Страница 2: ...k must be carried out on the device cut off the electric supply first Do not use devices with automatic or time reset or which may be reset accidentally 4 Use suitable automatic protection devices in...

Страница 3: ...nimum flow rate to activate domestic water flow meter 2 l min 0 3 Electric supply 230 V ac 10 50Hz Max power consumption 80 W Protection class IP 40 Pump UPM3 15 70 Actuators 24 V stepper motor Probes...

Страница 4: ...be 10 Pressure gauge 11 Safety thermostat 12 130 mm heat meter template 13 1 4 F pressure test port 14 Connection for M10x1 heat meter return probe 15 Primary drain cock 16 Connection for M10x1 heat m...

Страница 5: ...kflow preventer code 572120 proceed as follows remove the nuts shown in the figure with letter A Hydraulic installation Preliminary operations installation without template After having established th...

Страница 6: ...tem in order to remove any residue or impurities that could endanger correct operation of the HIU In order to facilitate these operations a manual bypass flushing valve is available code 789110 N B In...

Страница 7: ...pipe To tighten the nuts apply maximum tightening torque of 25 Nm taking account of the indications of the heat meter manufacturer install the flow probe in the M10 pocket B Please refer to the heat m...

Страница 8: ...directed toward the exterior of the HIU using the pathways provided in the insulation and on the frame All the low voltage lines must be routed through a single dedicated cable raceway using the path...

Страница 9: ...necessary restore the pre charge value shown in the technical specifications Filling the user system SATK32 series HIU can be fitted with a charging unit equipped with a backflow preventer F check va...

Страница 10: ...ng modes OFF DHW only summer mode Heating DHW winter mode Heating only Selecting set points current time and comfort function Press the set key repeatedly to set the current time set point temperature...

Страница 11: ...arious parameters which can then be edited pressing and rotating knob R Technical parameter t00 Primary limit set return temperature in heating mode Primary limit set return temperature in DHW mode Co...

Страница 12: ...ng To set the flow temperature press the SET key until the symbol in the red circle appears for the return temperature limit press the key until the symbols in the green circle are displayed Use the R...

Страница 13: ...7 1 freezes the operating set points to prevent inadvertent modifications by the user The comfort function can be alternatively preheating of the DHW plate heat exchanger or management of DHW recircul...

Страница 14: ...posed by controlling the maximum opening of the primary circuit modulating valve Since latter is controlled by a differential pressure limiter it is possible to supply direct correspondence between th...

Страница 15: ...es a sequence of LEDs showing the instantaneous power consumption 1 yellow LED lit power between 0 and 25 of Pmax 2 yellow LEDs lit power between 25 and 50 of Pmax 3 yellow LEDs lit power between 50 a...

Страница 16: ...must be set to 1 2 4 7 This value t05 7 is set by default example 2 Distinction of consumption for DHW production from total consumption in combination with heat meter equipped with dedicated function...

Страница 17: ...ire twisted cable Compliance with this requirement becomes even more significant the more extensive the RS 485 network If alternatively a shielded wire is used the shield must be connected solely on t...

Страница 18: ...nd disabled Any requests to run cycles not associated to the previous one will continue to run normally Heating flow probe fault Error code 5 Domestic hot water probe fault Error code 6 Return probe f...

Страница 19: ...o be interfaced with controllers managing the heating and DHW production services by means of pre paid type logic The HIU interprets an open contact as credit available Closing the contact disables th...

Страница 20: ...ween 0 9 and 1 2 bar Restore the pressure value if necessary Re open the shut off valves and restore secondary circuit pressure to a value between 1 3 and 1 7 bar Check for the absence of any liquid d...

Страница 21: ...tuator see previous paragraph Extract the obturator unscrewing the locking nut F Replace the obturator screw on the locking nut F and then fit the actuator Insert the fixing clip respecting the correc...

Страница 22: ...r partly clogged call qualified personnel to have it serviced modulating valve actuator faulty call qualified personnel to have it replaced DHW temperature probe cable inverted with heating probe rest...

Страница 23: ...in charge of system electronic regulator not working call qualified personnel to have it replaced primary circuit flow rate insufficient contact person in charge of system centralised system not work...

Страница 24: ...s external sensor prepayment auxilliary microswitch Modbus if required been carried out 15 Has the remote user interface been configured for installation on board thermostat function disabled inside t...

Отзывы: