16

Auxiliary microswitch

Event/condition

Value

DHW tapping in progress

1

Heating cycle in progress

2

Comfort cycle (pre-heating/recirculation) in progress

4

HIU OFF

8

Error not active

16

Error active

32

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

The HIU is equipped with a contact, driven by a relay incorporated in
the circuit board, the intervention logic of which can be programmed
in accordance with requirements by setting technical parameter t05.

Each  event  linked  to  operation  of  the  HIU  is  linked  to  a  numerical
value, according to the following table:

Closing of the contact on the occurrence of multiple events conditions
is programmed by setting parameter t05 to a value corresponding to
the sum of the single events/conditions.
We give some practical examples below:

example 1 - Driving an external primary flow pump, normally OFF.

The  contact  must  be  closed  if  any  HIU  function  is  active  (DHW
production, heating, pre-heating)

Parameter t05 must be set to: 1 + 2 + 4 = 7

This value (t05 = 7) is 

set by default

.

example 2 - Distinction of consumption for DHW production from
total consumption (in combination with heat meter equipped with
dedicated function)

The contact must be closed both if DHW tapping is in progress and if
activation  of  the  comfort  function  is  requested  (pre-heating  or
recirculation).

Parameter t05 must be set to 1 + 4 = 5.

Closing  of  the  microswitch  is  shown  on  the  user  interface  by  the
symbols shown alongside.

N.B.  if  the  DHW  recirculation  function  is  enabled  with  t02  =  1
(see  page  13)  the  auxiliary  microswitch  intervention  logic
described above is not operational. In this case, the contact is
used to control the recirculation pump.

N.B.:  the  auxiliary  microswitch  can  be  used  to  drive  electric
loads directly, taking account of the following operating limits:

- Max voltage:                                                                     230 Vac
- Max current:                                                                             3 A

If  the  electric  load  to  be  controlled  is  not  included  within  the
parameters indicated an external relay must be interposed.

Connection

For information on how to access the dedicated terminals, consult the
“auxiliary microswitch” section on page 19.

Содержание SATK32 Series

Страница 1: ...de 10 Commissioning 9 Electrical installation 8 Hydraulic installation 5 Hydraulic components and diagram 4 Dimensions Technical specifications 3 Safety instructions 2 DHW function Comfort functions P...

Страница 2: ...k must be carried out on the device cut off the electric supply first Do not use devices with automatic or time reset or which may be reset accidentally 4 Use suitable automatic protection devices in...

Страница 3: ...nimum flow rate to activate domestic water flow meter 2 l min 0 3 Electric supply 230 V ac 10 50Hz Max power consumption 80 W Protection class IP 40 Pump UPM3 15 70 Actuators 24 V stepper motor Probes...

Страница 4: ...be 10 Pressure gauge 11 Safety thermostat 12 130 mm heat meter template 13 1 4 F pressure test port 14 Connection for M10x1 heat meter return probe 15 Primary drain cock 16 Connection for M10x1 heat m...

Страница 5: ...kflow preventer code 572120 proceed as follows remove the nuts shown in the figure with letter A Hydraulic installation Preliminary operations installation without template After having established th...

Страница 6: ...tem in order to remove any residue or impurities that could endanger correct operation of the HIU In order to facilitate these operations a manual bypass flushing valve is available code 789110 N B In...

Страница 7: ...pipe To tighten the nuts apply maximum tightening torque of 25 Nm taking account of the indications of the heat meter manufacturer install the flow probe in the M10 pocket B Please refer to the heat m...

Страница 8: ...directed toward the exterior of the HIU using the pathways provided in the insulation and on the frame All the low voltage lines must be routed through a single dedicated cable raceway using the path...

Страница 9: ...necessary restore the pre charge value shown in the technical specifications Filling the user system SATK32 series HIU can be fitted with a charging unit equipped with a backflow preventer F check va...

Страница 10: ...ng modes OFF DHW only summer mode Heating DHW winter mode Heating only Selecting set points current time and comfort function Press the set key repeatedly to set the current time set point temperature...

Страница 11: ...arious parameters which can then be edited pressing and rotating knob R Technical parameter t00 Primary limit set return temperature in heating mode Primary limit set return temperature in DHW mode Co...

Страница 12: ...ng To set the flow temperature press the SET key until the symbol in the red circle appears for the return temperature limit press the key until the symbols in the green circle are displayed Use the R...

Страница 13: ...7 1 freezes the operating set points to prevent inadvertent modifications by the user The comfort function can be alternatively preheating of the DHW plate heat exchanger or management of DHW recircul...

Страница 14: ...posed by controlling the maximum opening of the primary circuit modulating valve Since latter is controlled by a differential pressure limiter it is possible to supply direct correspondence between th...

Страница 15: ...es a sequence of LEDs showing the instantaneous power consumption 1 yellow LED lit power between 0 and 25 of Pmax 2 yellow LEDs lit power between 25 and 50 of Pmax 3 yellow LEDs lit power between 50 a...

Страница 16: ...must be set to 1 2 4 7 This value t05 7 is set by default example 2 Distinction of consumption for DHW production from total consumption in combination with heat meter equipped with dedicated function...

Страница 17: ...ire twisted cable Compliance with this requirement becomes even more significant the more extensive the RS 485 network If alternatively a shielded wire is used the shield must be connected solely on t...

Страница 18: ...nd disabled Any requests to run cycles not associated to the previous one will continue to run normally Heating flow probe fault Error code 5 Domestic hot water probe fault Error code 6 Return probe f...

Страница 19: ...o be interfaced with controllers managing the heating and DHW production services by means of pre paid type logic The HIU interprets an open contact as credit available Closing the contact disables th...

Страница 20: ...ween 0 9 and 1 2 bar Restore the pressure value if necessary Re open the shut off valves and restore secondary circuit pressure to a value between 1 3 and 1 7 bar Check for the absence of any liquid d...

Страница 21: ...tuator see previous paragraph Extract the obturator unscrewing the locking nut F Replace the obturator screw on the locking nut F and then fit the actuator Insert the fixing clip respecting the correc...

Страница 22: ...r partly clogged call qualified personnel to have it serviced modulating valve actuator faulty call qualified personnel to have it replaced DHW temperature probe cable inverted with heating probe rest...

Страница 23: ...in charge of system electronic regulator not working call qualified personnel to have it replaced primary circuit flow rate insufficient contact person in charge of system centralised system not work...

Страница 24: ...s external sensor prepayment auxilliary microswitch Modbus if required been carried out 15 Has the remote user interface been configured for installation on board thermostat function disabled inside t...

Отзывы: