OPERATIONS TO BE PERFORMED

Force an actuators reset by switching the HIU power supply OFF and then ON

Visually check for the absence of leaks and/or anomalies

Check for possible active errors shown on the user interface

Test correct operation of the pump/modulating valve by closing the thermostat contact or forcing it to close

Clean the strainers: on the primary flow line, on the secondary return line, upstream of the domestic water flow meter

Check for the absence of internal leakage through the modulating valves when none of the services are active

Check correct setting of the set points (DHW and heating). Unless explicitly requested by the user or for normative reasons, a DHW temperature 

set point of 50°C or lower is recommended

With the primary circuit at working temperature, check that the DHW flow rate at the correct temperature is sufficient

Periodic maintenance

The following checks must be carried out at least once very 12 months, in accordance with the prescriptions of standard EN 806-5.

Maintenance

All maintenance procedures should be carried out by an authorised 
technician. Regular maintenance guarantees better efficiency and 
helps to save energy.
Before carrying out any maintenance, repair or part replacement work, 
proceed as follows:
-   Cut off the electric supply
-   Remove the cover
-   Close the shut-off valves
-   Empty the heat interface unit using the drain cocks provided.

Exchanger replacement

-   As a preliminary step, remove the flow sensor (refer to “replacing 

the DHW priority flow meter”, on page 21) and position it 
where it cannot be reached by any dripping liquid. 

 

Remove the exchanger, loosening 
the 2 hex socket head screws fixing it in place (A) 

-   Replace the exchanger and the O-rings. 
-   Tighten the two fixing screws (A) after having checked that the 

O-rings are correctly positioned. Tightening torque 3-3,5 Nm.

N.B.

 Make sure to respect the correct orientation of the plate heat 

exchanger when fitting it back.

Parameter

Meaning

Settings

t00

Not used

-

t01

Heating flow temperature control

0 = fixed set point

1 = fixed set point with RTL

2 = compensated on return temperature

3 = weather compensated

t02

DHW comfort mode

0 = pre-heating of the heat exchanger

1 = DHW recirculation

t03

Maximum % opening of the heating modulating valve (SATK2230./SATK2240. only)

From 50 to 100

t04

Maximum % opening of the DHW modulating valve

From 50 to 100

t05

Configuration of the closing logic of the auxilliary microswitch

See page 16

t06

DHW temperature control

0 = fixed set point

1 = fixed set point with RTL

t07

Freezing of return temperature set points

0 = all temperature settings can be modified

1 = return temperature limits are freezed

t08

Anti-legionella

0 = disabled

1 = enabled between 3:00 to 3:30 a.m.

t09

Duration of a DHW recirculation cycle

1 unit = 10 seconds

Summary of the technical parameters

Here follows a summary of the meaning and possible settings of the technical parameters:

Содержание SATK22107

Страница 1: ...mestic hot water capacity 50 kW 1 With primary pump SATK22405 Direct wall mounted HIU for HIGH temp heating Domestic hot water capacity 60 kW 1 With primary pump SATK22407 Direct wall mounted HIU for...

Страница 2: ...acteristics of both units into consideration 10 An combination coupling could compromise the operation of the device and or system IMPORTANT Risk of electric shock Live parts Shut off the electric sup...

Страница 3: ...primary circuit Dp 600 kPa 6 bar Domestic water circuit max flow rate 24 l min 0 4 l s Minimum flow rate to activate domestic water flow meter 2 l min 0 3 Electric supply 230 V ac 10 50Hz Max power c...

Страница 4: ...r primary circuit air vent Characteristic components SATK2210 LOW temperature Hydraulic diagram SATK2210 and SATK2220 TS TA 2 V V V V V V 3 4 7 12 13 5 6 8 9 10 11 21 14 15 19 24 20 17 16 17 22 23 25...

Страница 5: ...draulic diagram SATK2230 and SATK2240 TS TA 2 V V V V V V 3 4 7 12 13 5 6 8 9 10 11 21 14 15 19 24 20 17 16 17 22 23 25 TA 2 V V V V V V 3 4 7 5 6 8 9 10 11 21 13 14 19 22 20 23 16 17 18 SATK2210 only...

Страница 6: ...out template code 789023 Hydraulic installation Preliminary operations installation without template After having established the point of installation of the appliance perform the following operation...

Страница 7: ...bottom Connections on the top Heat meter installation The HIU is fitted to house a compact heat meter with incorporated return probe with 1 threaded connections and length of 130 mm Before carrying o...

Страница 8: ...directed toward the exterior of the HIU using the pathways provided in the insulation and on the frame All the low voltage lines must be routed through a single dedicated cable raceway using the path...

Страница 9: ...ntrol Refer to the dedicated user manual for the procedure Filling the central heating system Open the shut off valves on the connections to the centralised line and in the central heating system proc...

Страница 10: ...riarmabile funzione scaldamassetto R mode ACS ON OFF Risc ON OFF set Ora giorno corrente Temperature di set point k regolazione climatica day night Set diurno nottu prog Programmazione oraria riscalda...

Страница 11: ...oint k regolazione climatica day night Set diurno notturno temp Visualizzazione temperature set point ambiente sonde prog Programmazione oraria riscaldamento e funzione comfort reset Reset errore riar...

Страница 12: ...ed the display shows the symbol OPTIONAL SETTING weather compensation technical parameter t01 3 When the function is enabled the flow temperature is calculated based on the temperature detected by the...

Страница 13: ...menu see access to technical menu below Parameter t07 1 freezes the operating set points to prevent inadvertent modifications by the user The comfort function can be alternatively preheating of the DH...

Страница 14: ...ntrolling the maximum opening of the primary circuit modulating valve Since latter is controlled by a differential pressure limiter it is possible to supply direct correspondence between the opening p...

Страница 15: ...wo seconds and then press the same key repeatedly until reaching the required characteristic refer to the figure below Having identified the required characteristic head flow rate chart shown below wa...

Страница 16: ...xternal primary flow pump normally OFF The contact must be closed if any HIU function is active DHW production heating pre heating Parameter t05 must be set to 1 2 4 7 example 2 Distinction of consump...

Страница 17: ...ire twisted cable Compliance with this requirement becomes even more significant the more extensive the RS 485 network If alternatively a shielded wire is used the shield must be connected solely on t...

Страница 18: ...code 76 Corrective action Normal operating conditions are restored automatically once the faulty safety valve works properly again reriscaldo circolo Impostazione default limitazione portata massima...

Страница 19: ...PAID AUX RS 4 IN IN IN OUT IN OUT EXP PORT OTS RT PREPAID AUX RS 485 BUS IN IN IN OUT IN OUT EXP PORT OTS RT PREPAID AUX RS 485 BUS IN IN IN OUT IN OUT EXP PORT OTS RT PREPAID AUX RS 485 BUS IN IN IN...

Страница 20: ...pty the heat interface unit using the drain cocks provided Exchanger replacement As a preliminary step remove the flow sensor refer to replacing the DHW priority flow meter on page 21 and position it...

Страница 21: ...e previous paragraph Extract the obturator unscrewing the locking nut F Replace the obturator screw on the locking nut F and then fit the actuator Insert the fixing clip respecting the correct directi...

Страница 22: ...ature set point disable the function primary circuit strainer of the HIU clogged call qualified personnel to have it serviced exchanger partly clogged call qualified personnel to have it serviced modu...

Страница 23: ...on in charge of system electronic regulator not working call qualified personnel to have it replaced primary circuit flow rate insufficient contact person in charge of system centralised system not wo...

Страница 24: ...if required been carried out 13 Has the remote user interface been configured for installation on board thermostat function disabled inside the apartment with thermostat function enabled 14 Have the h...

Отзывы: