background image

1

SATK series wall-mounted direct Heat Interface Unit

Serie SATK22

INSTRUCTIONS FOR INSTALLATION, COMMISSIONING AND MAINTENANCE

Product range

SATK22103

   Direct wall-mounted HIU for LOW temperature

 heating. 

Domestic hot water capacity 50 kW

(1)

.

SATK22105

   Direct wall-mounted HIU for LOW temperature

 heating. 

Domestic hot water capacity 60 kW

(1)

.

SATK22107

   Direct wall-mounted HIU for LOW temperature  

 

heating. For low temperature heating networks.

SATK22203

   Direct wall-mounted HIU for MEDIUM temp.

 heating. 

Domestic hot water capacity 50 kW

(1)

.

SATK22205

   Direct wall-mounted HIU for MEDIUM temp.

 heating. 

Domestic hot water capacity 60 kW

(1)

.

SATK22207

   Direct wall-mounted HIU for MEDIUM temperature 

 

heating. For low temperature heating networks

)

.

SATK22303

   Direct wall-mounted HIU for HIGH temp.

 heating. 

Domestic hot water capacity 50 kW

(1)

.

SATK22305

   Direct wall-mounted HIU for HIGH temp.

 heating. 

Domestic hot water capacity 60 kW

(1)

.

SATK22307

   Direct wall-mounted HIU for HIGH temperature 

 

heating. For low temperature heating networks.

SATK22403

   Direct wall-mounted HIU for HIGH temp.

 heating. 

Domestic hot water capacity 50 kW

(1)

.

 

With primary pump.

SATK22405

   Direct wall-mounted HIU for HIGH temp.

 heating. 

Domestic hot water capacity 60 kW

(1)

.

 

With primary pump.

SATK22407

   Direct wall-mounted HIU for HIGH temperature 

 

heating. For low temperature heating networks. 

 

H0003192.01

www.caleffi.com

(1)  Primary side head > 50 kPa, primary flow temperature 70°C,
      DHW 10 - 50°C

CONTENTS

Function 

The SATK series HIU allows independent control of heat regulation and 
domestic hot water production within centralised heating systems or systems 
served by district heating networks.
The heat interface unit features exceptional flexibility of installation and remote 
controllable smart electronic functions designed to enhance efficiency of the 
system.

Heating function

12

Remote user interface quick guide

10

Commissioning

9

Electrical installation

8

Hydraulic installation

5

Hydraulic components and diagram

4

Dimensions - Technical specifications

3

Safety instructions

2

DHW function - Comfort functions

Primary flow rate limitation

Circulator - curves and setting

Auxiliary microswitch

Modbus

Safety and alarms

Electronic circuit board

Periodic maintenance

Troubleshooting

Commissioning check-list

20

19

18

17

16

15

14

13

24

22

Anti-legionella function

14

All languages 

are available on:

 

I     FR    NL

Содержание SATK22107

Страница 1: ...mestic hot water capacity 50 kW 1 With primary pump SATK22405 Direct wall mounted HIU for HIGH temp heating Domestic hot water capacity 60 kW 1 With primary pump SATK22407 Direct wall mounted HIU for...

Страница 2: ...acteristics of both units into consideration 10 An combination coupling could compromise the operation of the device and or system IMPORTANT Risk of electric shock Live parts Shut off the electric sup...

Страница 3: ...primary circuit Dp 600 kPa 6 bar Domestic water circuit max flow rate 24 l min 0 4 l s Minimum flow rate to activate domestic water flow meter 2 l min 0 3 Electric supply 230 V ac 10 50Hz Max power c...

Страница 4: ...r primary circuit air vent Characteristic components SATK2210 LOW temperature Hydraulic diagram SATK2210 and SATK2220 TS TA 2 V V V V V V 3 4 7 12 13 5 6 8 9 10 11 21 14 15 19 24 20 17 16 17 22 23 25...

Страница 5: ...draulic diagram SATK2230 and SATK2240 TS TA 2 V V V V V V 3 4 7 12 13 5 6 8 9 10 11 21 14 15 19 24 20 17 16 17 22 23 25 TA 2 V V V V V V 3 4 7 5 6 8 9 10 11 21 13 14 19 22 20 23 16 17 18 SATK2210 only...

Страница 6: ...out template code 789023 Hydraulic installation Preliminary operations installation without template After having established the point of installation of the appliance perform the following operation...

Страница 7: ...bottom Connections on the top Heat meter installation The HIU is fitted to house a compact heat meter with incorporated return probe with 1 threaded connections and length of 130 mm Before carrying o...

Страница 8: ...directed toward the exterior of the HIU using the pathways provided in the insulation and on the frame All the low voltage lines must be routed through a single dedicated cable raceway using the path...

Страница 9: ...ntrol Refer to the dedicated user manual for the procedure Filling the central heating system Open the shut off valves on the connections to the centralised line and in the central heating system proc...

Страница 10: ...riarmabile funzione scaldamassetto R mode ACS ON OFF Risc ON OFF set Ora giorno corrente Temperature di set point k regolazione climatica day night Set diurno nottu prog Programmazione oraria riscalda...

Страница 11: ...oint k regolazione climatica day night Set diurno notturno temp Visualizzazione temperature set point ambiente sonde prog Programmazione oraria riscaldamento e funzione comfort reset Reset errore riar...

Страница 12: ...ed the display shows the symbol OPTIONAL SETTING weather compensation technical parameter t01 3 When the function is enabled the flow temperature is calculated based on the temperature detected by the...

Страница 13: ...menu see access to technical menu below Parameter t07 1 freezes the operating set points to prevent inadvertent modifications by the user The comfort function can be alternatively preheating of the DH...

Страница 14: ...ntrolling the maximum opening of the primary circuit modulating valve Since latter is controlled by a differential pressure limiter it is possible to supply direct correspondence between the opening p...

Страница 15: ...wo seconds and then press the same key repeatedly until reaching the required characteristic refer to the figure below Having identified the required characteristic head flow rate chart shown below wa...

Страница 16: ...xternal primary flow pump normally OFF The contact must be closed if any HIU function is active DHW production heating pre heating Parameter t05 must be set to 1 2 4 7 example 2 Distinction of consump...

Страница 17: ...ire twisted cable Compliance with this requirement becomes even more significant the more extensive the RS 485 network If alternatively a shielded wire is used the shield must be connected solely on t...

Страница 18: ...code 76 Corrective action Normal operating conditions are restored automatically once the faulty safety valve works properly again reriscaldo circolo Impostazione default limitazione portata massima...

Страница 19: ...PAID AUX RS 4 IN IN IN OUT IN OUT EXP PORT OTS RT PREPAID AUX RS 485 BUS IN IN IN OUT IN OUT EXP PORT OTS RT PREPAID AUX RS 485 BUS IN IN IN OUT IN OUT EXP PORT OTS RT PREPAID AUX RS 485 BUS IN IN IN...

Страница 20: ...pty the heat interface unit using the drain cocks provided Exchanger replacement As a preliminary step remove the flow sensor refer to replacing the DHW priority flow meter on page 21 and position it...

Страница 21: ...e previous paragraph Extract the obturator unscrewing the locking nut F Replace the obturator screw on the locking nut F and then fit the actuator Insert the fixing clip respecting the correct directi...

Страница 22: ...ature set point disable the function primary circuit strainer of the HIU clogged call qualified personnel to have it serviced exchanger partly clogged call qualified personnel to have it serviced modu...

Страница 23: ...on in charge of system electronic regulator not working call qualified personnel to have it replaced primary circuit flow rate insufficient contact person in charge of system centralised system not wo...

Страница 24: ...if required been carried out 13 Has the remote user interface been configured for installation on board thermostat function disabled inside the apartment with thermostat function enabled 14 Have the h...

Отзывы: