FAULT DESCRIPTION

INDICATIONS

POSSIBLE CAUSE OF FAULT

OPERATIONS TO BE PERFORMED

The room 

is not reaching

the desired

temperature

CH LED on

heating cycle temperature set point too low

increase set point

chrono-thermostat temperature setting incorrect

check programming of chrono-

thermostat

HIU strainer clogged

call qualified personnel to have it

serviced

heating valve actuator faulty

call qualified personnel to have it

replaced

heating valve obturator blocked

call qualified personnel to have it

replaced

modulating valve actuator connector disconnected

reconnect actuator connector

DHW temperature probe cable inverted with heating

probe

restore correct connection

presence of air in the system

vent the system

pump (if present) not working

call qualified personnel to have it

replaced

pump cable (if present) not connected

restore connection

possible system shut-off valves/terminals closed

open the valves

centralised system temperature insufficient

contact person in charge of system

electronic controller not working

call qualified personnel to have it

replaced

primary circuit flow rate insufficient

contact person in charge of system

centralised system not working

contact person in charge of system

CH LED off

chrono-thermostat time setting incorrect

check programming of chrono-

thermostat

chrono-thermostat not working

check chrono-thermostat

all LEDs are off

Electric supply cut off

restore HIU electric supply

Protection fuse burnt out

call qualified personnel to have it

replaced

FAULT LED on + error

code 5 active

heating temperature probe faulty

call qualified personnel to have it

replaced

FAULT LED on + error

code 15 active

compensation temperature probe faulty

call qualified personnel to have it

replaced

FAULT LED on + error

code 69 active

safety thermostat cut-out

call qualified personnel to have it

serviced

FAULT LED on + error

code 76 active

safety relief valve faulty

call qualified personnel to have it

serviced

FAULT LED on + error

code 79 active

incorrect switch setting

restore correct switch setting

FAULT LED on +

error code 80 active

incorrect switch setting

restore correct switch setting

Start-up of the

heat interface

unit heating

function triggers
the safety circuit

breaker

All LEDs are off

pump connector inserted the wrong way round

check that the pump cable connector is

inserted the right way round

Содержание SATK20 Series

Страница 1: ...ms Product range SATK20103HE Direct wall mounted HIU for LOW temperature heating instantaneous domestic hot water production power capacity 40 kW SATK20203HE Direct wall mounted HIU for MEDIUM tempera...

Страница 2: ...high intensity electromagnetic fields This device cannot be used in areas at risk of explosion or fire 3 The device must be connected to an independent bipolar switch If work has to be done on the de...

Страница 3: ...ell cover EPP Heat exchanger brazed stainless steel SATK20305 technical specifications Medium water Maximum percentage of glycol 30 Maximum medium temperature 85 C Maximum working pressure primary cir...

Страница 4: ...ontact a qualified technician to request a thorough check of the electrical system Electrical safety of the appliance is only achieved when it is correctly connected to an effective earthing system ma...

Страница 5: ...centralised system It is advisable to install manual shut off valves not supplied also on the bottom connections to the apartment circuits Before installation it is recommended to carry out accurate...

Страница 6: ...r steady illumination of the LEDs ON Electric supply 230 V ac DHW Domestic cycle CH Heating cycle FAULT Fault detected Domestic cycle Heating cycle Operating principle All heating and domestic hot wat...

Страница 7: ...lty safety valve is working properly again Thermal safety valve fault SATK20103HE LOW temperature Error code 76 76 Removing a fault Normal operating conditions are restored automatically once the faul...

Страница 8: ...ner heat meter flow probe pocket 18 Primary circuit shut off valves SATK20103HE LOW temperature heat interface unit with high efficiency pump Functional characteristics Heating range 45 75 C Set point...

Страница 9: ...a temperature of 45 C Once the maximum set point has been reached the function is executed following the same procedures in reverse from the maximum set point to the minimum set point This function h...

Страница 10: ...ctory settings 1 2 3 4 5 6 4 ON Functional characteristics Maximum heating temp 85 C ON OFF regulation DHW production range 42 60 C Optional functions Domestic cycle DHW pre heating function 1 2 3 4 5...

Страница 11: ...circulate at the temperature supplied by the central heating system ON OFF regulation The valve is closed on completion of the heating cycle The active heating cycle is signalled by lighting of the ye...

Страница 12: ...inserted Replacing the valve actuator Disconnect the actuator cable lightly pressing the tab on the connector and extracting it see page 13 ref 4 8 Extract the fixing clip D and then the actuator Posi...

Страница 13: ...pulito Room thermostat Volt free connection This connection may not be available To be wired during installation Room thermostat not supplied potential free line MAX 30 m 6 ON Dip switch 6 configurati...

Страница 14: ...d heat exchanger partly clogged call qualified personnel to have it serviced modulating valve actuator faulty call qualified personnel to have it replaced valve obturator blocked in intermediate posit...

Страница 15: ...ced primary circuit flow rate insufficient contact person in charge of system centralised system not working contact person in charge of system CH LED off chrono thermostat time setting incorrect chec...

Страница 16: ...ve result Are the connections compliant with specifications and made in accordance with best practices 13 all Are the shut off valves open 14 all Has the visual inspection of the hydraulic connections...

Отзывы: