SAFETY INSTRUCTION

This safety alert symbol will be used in this manual to draw attention to safety related

instructions. When used, the safety alert symbol means

ATTENTION! BECOME ALERT!

YOUR SAFETY IS INVOLVED! FAILURE TO FOLLOW THESE INSTRUCTIONS MAY

RESULT IN A SAFETY HAZARD.

CAUTION:

All work must be performed by qualified personnel trained in the

proper application, installation, and maintenance of systems in accordance

with all applicable codes and ordinances.

CAUTION:

Over-tightening and breakage can occur with the use of Teflon

®

pipe joint compounds. Teflon

®

provides lubricity so that care must be

exercised not to over-tighten joints. Failure to follow these instructions

could result in property damage and /or personal injury.

WARNING:

System fluids are under pressure or temperature can be

hazardous. Be sure the pressure has been reduced to zero and the

system temperature is below 100°F (38°C). Failure to follow these

instructions could result in property damage and/or personal injury.

WARNING:

Clean the pipes of any debris, rust, incrustations, welding slag

and any other contaminants. For optimal operation, air in the system must

be removed.

Installation

Install the FlowCal

TM

automatic flow balancing valves on the circuit return pipe with flow

direction arrows indicating proper flow direction. It is important to allow easy access to the

FlowCal for inspection and maintenance.

The identification tag with the technical data must accompany the balancing valve after

installation. It is equipped with a special metal retaining ball chain especially useful when the

valve is enclosed with insulation.

Install a Y-strainer (series 120 on circuit supply pipe of the emitter coil to prevent clogging.

Strainers should be inspected and cleaned after start-up and twice per year thereafter.

FlowCal

TM

balancing valves may be installed in the pipe horizontally, vertically or at any angle.

For Sweat fittings: Union sweat tailpieces should be removed from the valve body for sweating to

the pipeline. Remove the

flow cartridg e (and adapter

for

larger

sizes)

and

FLOWCAL

 

Version

pressure port plugs while
sweating the fixed end into

RETURN

the pipeline. In addition,
wrap a wet cloth around the

EMITTER

ball valve portion of the

Y-Strainer Version

series 121 flow balancing

SUPPLY

valve (and the 120 Y-strainer)

when sweating in the integral

sweat body connection.

WARNING: 

This product can expose you to chemicals including lead, which is 

known to the State of California to cause cancer and birth defects or other 
reproductive harm. For more information go to www.P65Warnings.ca.gov.