Installation

The installation of SEP4™ should only be done by qualified personnel in 

accordance with current legislation. The SEP4™ is installed between the 

primary and secondary circuits, always in a vertical position. 

Hydraulic 

characteristics

The SEP4™ should be sized according to the maximum flow rate of either 

the primary circuit, or secondary circuit, whichever is largest.

Size

2"

2

1

2

"

3"

4"

5”

6"

8"

10"

12"

14"

gpm

60

80

124

247

300

484

792

1330 1850 2500

m

3

/h

13.6

18.2

28.2

56

68

110

180

302

420

568

l/s

3.8

5.0

7.8

15.6

19

30.5

50

84

117

158

Gallons

4.0

4.0

8.0

8.0

23

23

95

175

255

450

liters

15.1

15.1

30

30

87

87

360

662

965

1703

Technical specifications of insulation
Inner part

Material:   

rigid closed cell expanded polyurethane foam

Thickness:  

2 3/8” (60 mm)

Density:  

2.8 lb/ft

3

 (45 kg/m

3

)

Thermal conductivity: 

6 BTU·in/hr·ft

2

·°F (0.023 W/(m·K)

Temperature range: 

32–220°F 

(0–105°C) 

Outer part

Material:   

Embossed aluminium

Thickness:  

7-mil (0.70 mm)

Fire resistance (DIN 4102): 

Class 1

Head covers

Heat formed material: 

PS