background image

Low lead high-flow thermostatic mixing valves

 

 

NA10341.03

© Copyright 2018 Caleffi

ASSE 1017

Function

The thermostatic mixing valve is used in systems producing domestic 
hot water or in radiant heating systems. Its function is to maintain the 
temperature of the mixed water supplied to the user at a constant set 
value when there are variations in the supply pressure and temperature 
of the incoming hot and cold water or in the flow rate.
The 5231 series thermostatic mixing valves are ASSE 1017 approved for 
point of distribution and are designed specifically for systems requiring 
high flow rates and precise, stable temperature control. Optional 
stainless steel inlet port check valves are available separately, for field 
installation only.

Product range

5231 series thermostatic mixing valve. NPT male and sweat  union 
connections, sizes 1", 1-1/4", 1-1/2", 2".  Inlet port check valve s and 
outlet temperature gauge optional.

Technical characteristics

Materials:

  - body: 

DZR low-lead brass (<0.25% lead content) 

 

- shutter: 

PPSG40 

 

- springs: 

stainless steel 

 

- seals: 

peroxide-cured EPDM 

 

- check valve extension (field installed): 

stainless steel 

www.caleffi.com

5231 Series

INSTALLATION AND COMMISSIONING MANUAL

Suitable fluids: 

water, glycol solutions

Max. percentage of glycol: 

30% glycol solution

Mixed temperature adjustment range: 

95 – 150°F (32 – 66°C)

Temperature stability: 

± 3°F (± 2°C)

Max. operating differential pressure (static): 

200 psi (14 bar)

Max. operating differential pressure (dynamic): 

75 psi (5 bar)

Hot water inlet temperature range: 

120 – 195°F (49 – 91°C)

Cold water inlet temperature range: 

39 – 80°F (3.9 – 26.6°C)

Max. inlet pressure ratio (H/C or C/H) for optimum performance: 

2:1 

Min. temp. difference between hot inlet and mixed outlet for optimum perf:         20°F (11°C)

Max. water hardness: 

10 grains

Certified to: 
1. ASSE 1017/CSA B125.3, certified by ICC-ES, file PMG-1357. 

2. NSF/ANSI 372-2011, Drinking Water System Components-Lead Content Reduction of 

Lead in Drinking Water Act, California Health and Safety Code 116875 S.3874, Reduction 

of Lead in Drinking Water Act, certifed by ICC-ES, file PMG-1360.

1

Содержание 5231 Series

Страница 1: ...cal characteristics Materials body DZR low lead brass 0 25 lead content shutter PPSG40 springs stainless steel seals peroxide cured EPDM check valve extension field installed stainless steel www calef...

Страница 2: ...operate correctly and may endanger the user CAUTION Make sure that all the connecting pipework is water tight CAUTION When making the water connections make sure that the pipework connecting the therm...

Страница 3: ...des syst mes conform ment aux codes et r glements locaux ATTENTION Siler ducteurdepression termostaticoregolabile n estpasinstall mis en service et entretenu correctement selon les instructions conten...

Страница 4: ...20 F 11 C to ensure the correct operation and maximum pressure difference between the hot and cold inlet parts no greater than 2 1 ratio Softened water use is highly recommended as the warranty is vo...

Страница 5: ...10 2 0 5 0 115 172 75 Flow should never exceed standards for pipe size and material Size Connection Model Min Flow GPM Max Flow GPM CV 1 NPT 523160A 4 4 40 7 1 Sweat 523168A 4 4 40 7 1 NPT 523170A 4...

Страница 6: ...s may affect performance and the manufacturer s product guarantee Softened water use is highly recommended as the warranty is voided if used on water with hardness greater than 10 grains The installat...

Страница 7: ...1 1 4 NPT 4 1 8 8 1 4 7 3 4 4 5 16 3 3 8 7 0 523177A 1 1 4 SWT 3 3 8 6 3 4 7 5 8 4 1 8 3 3 8 9 0 523178A 1 1 4 SWT 3 3 8 6 3 4 7 3 1 2 3 3 8 7 0 523180A 1 1 2 NPT 5 1 8 10 1 4 9 3 16 5 7 16 3 3 4 17 5...

Страница 8: ...5 16 3 3 8 9 0 1 1 4 SWT 4 3 4 9 5 8 7 5 8 4 1 8 3 3 8 11 0 1 1 4 SWT 4 3 4 9 5 8 7 3 1 2 3 3 8 9 0 NA10367 1 1 2 NPT 7 3 8 14 3 4 9 3 16 5 7 16 3 3 4 19 1 1 2 SWT 6 1 4 12 5 8 8 1 8 4 3 8 3 3 4 19 2...

Страница 9: ...ptor fits high flow 5231 series mixing valves Removable gauge fits into temperature well Gauge dial is 2 diameter and scale from 30 210 F Low lead brass body Code Description Lbs NA10315 1 sweat with...

Страница 10: ...xed water temperature to 120 F in domestic hot water systems Maintenance Service tests should be carried out regularly to monitor the mixing valve performance as deterioration of performance could ind...

Страница 11: ...LEFFI CALEFFI 10 0 8 6 4 2 10 0 8 6 4 2 CALEFFI CALEFFI 10 0 8 6 4 2 10 0 8 6 4 2 10 0 8 6 4 2 10 0 8 6 4 2 T Key to symbols Safetyrelief valve Check valve Isolation valve Expansion vessel Filter Pump...

Страница 12: ...fitted Replace faulty check valves Fluctuating mixer water temperature a Erratic supply temperatures at the inlets of the valve b Starvation of the water supplies at the inlets of the valve c Incorrec...