Adjust the parameters referring to differential pressure
(signal 2) if a DPS is used:
•
Min Alarm:
If the minimum differential pressure is reached, the
relay is energised,
appears in the display, the LED
flashes green and an alarm message appears in the
submenu “Reports”.
Î
Select “Yes” or “No” to activate or deactivate the
function.
If this function is selected, the minimum value for the
alarm has to be adjusted.
Adjustment range: 0 ... 99.9 bar
Adj. values:
diff.-Pressure
Min Alarm
nO
Max Alarm nO
min alarm
yes
min
0.0 BAR
max alarm
yes
max
12.0 BAR
•
Max Alarm:
If the maximum differential pressure is reached, the
relay is energized,
appears in the display, the LED
flashes green and an alarm message appears in the
submenu “Reports”.
Î
Select “Yes” or “No” to activate or deactivate the
function.
If this function is selected, the maximum value for the
alarm has to be adjusted.
Adjustment range: 0 ... 99.9 bar
Heat quantity measurement
Heat quantity measurement is carried out by means of the
difference between the flow and the return temperature as
well as the measured flow rate. If the function is activated
(factory setting), make the following adjustments:
Adjustments for heat quantity measurement.
•
Heatmeter:
Heat quantity measurement can be activated or deacti-
vated with this option.
•
unit:
Î
Select a unit for the indication of the heat quantity
The units Wh or kJ can be selected.
•
Type:
Î
Select the type of heat transfer fluid
Water, Propylene, Ethylene or Tyfocor
®
LS can be se-
lected.
•
antifreeze:
Î
Adjust the concentration of propylene or ethylene
glycol in the heat transfer fluid
This adjustment channel is only visible if “Propylene” or
“Ethylene” is selected as “Type”.
Adjustment range: 20 ... 70 %.
adj. values:
Heatmeter
yes
unit
Wh
Type
wAtER
adj. values:
Unit
Wh
Type
Propylene
Antifreeze
38%
Note:
The parameters and adjustments have to be
selected and adjusted for sensor 2 as well. For
adjustment, please carry out the steps described
for sensor 1!