background image

Commissioning

After installation, the valve should be tested and commissioned in accordance with AS 4032.3,

as per the procedure outlined below or as specified by the local authority.

The following instructions should be read and understood prior to commissioning the Caleffi

2522HP series valve. If, under any circumstances, there are aspects of the installation/system

which do not comply with the requirements or the specifications as laid down, the valve must

not be put into service until it does comply.

1) Ensure that the system is thoroughly clean and free from debris prior to commissioning the

tempering valve.

2) Measure the mixed water temperature at the nearest outlet (we recommend using an

accurate digital thermometer).

3) The temperature of the mixed water supplied to an outlet primarily for personal hygiene

purposes shall be in accordance with the requirements of AS/NZS 3500.

4) Once the supply temperatures and normal operating conditions have stabilised, the valve

can be commissioned. The temperature setting can be adjusted by removing the cap and

rotating temperature adjustment spindle.

We suggest that the following sequence is followed when commissioning the valve.

a) Set the mixed water discharge temperature to the required temperature.

b) Measure the temperature of hot and cold water at the inlets of the valve.

c) Measure the temperature of discharged mixed water for high and low flow conditions.

d) Perform the thermal shut-off test, by isolating the cold water supply to the Caleffi 2522HP

valve and monitor the mixed water temperature. The outlet flow should quickly cease.

e) Restore the cold water supply to the valve and measure the mixed water temperature

when it has stabilised. The final temperature found during this test should not exceed the

set temperature by +3°C.

5) Once commissioning is completed, lock the temperature adjustment spindle using the

locking nut supplied and secure the cap back on to the valve to prevent tampering by

unauthorised persons.

6) Complete the “TEMPERING VALVE FITTED” label and affix it to the water heater (or where

required by the Local Authority).

8

Instantaneous
system

MAINS

SUPPLY

INSTANTA-

NEOUS
WATER

HEATER

Содержание 2522HP Series

Страница 1: ...meet the requirements of AS 4032 2 2005 Tempering valves and end ofline temperature actuated devices This particular series of tempering valves has been developed primarily for installation in solar h...

Страница 2: ...erature 55 C Maximum hot inlet temperature 100 C Maximum working pressure static 1400 kPa Maximum working pressure dynamic 500 kPa Minimum working pressure dynamic 20 kPa Maximum unbalanced dynamic su...

Страница 3: ...water entering the valve If there are variations of temperature or pressure at the inlets the internal element automatically reacts attempting to restore the original temperature setting Thermal shut...

Страница 4: ...er heater In order to maintain the set temperature the tempering valve must have a minimum flow rate of 4 l min When used in instantaneous hot water systems the most stable conditions are achieved wit...

Страница 5: ...5 8 7 4 1 2 6 9 1 CAP 3 4 7 9 8 5 6 3 2 VALVE BODY UNION NUT GASKET INSERT CHECK VALVE TAIL PIECE BODY INSERT STRAINER TEMPERATURE ADJUSTMENT SPINDLE LOCKING NUT Exploded diagram KIT A 5...

Страница 6: ...The hot and cold water supplies must be connected to the valve strictly in accordance with the indications on the body of the valve The inlets of the valves are clearly marked with the letter H Hot an...

Страница 7: ...lar system MAINS SUPPLY System without recirculation System with recirculation MAINS SUPPLY MAINS SUPPLY HOT WATER STORAGE HEATER HOT WATER STORAGE HEATER SOLAR HOT WATER STORAGE 7 Application diagram...

Страница 8: ...commissioned The temperature setting can be adjusted by removing the cap and rotating temperature adjustment spindle We suggest that the following sequence is followed when commissioning the valve a...

Страница 9: ...9 1 2 3 4 Temperature adjustment Remove the cap Direction of temperature adjustment Temperature adjustment Lock adjustment spindle with locking nut...

Страница 10: ...should be removed for cleaning by unscrewing the inlet union nuts and carefully pulling apart the connecting pipework B The built in check valves 7 can be accessed in a similar way to A Ensure freedom...

Страница 11: ...Starvation of the water supplies at the inlets of the valve c Incorrect commissioning of the valve a Insufficient water supplies b Fluctuations in supply pressures temperatures c Adverse effect create...

Страница 12: ...highly aggressive water in accordance with the current legislation treat the water before it enters the tempering valve This will avoid damage to the valve If the tempering valve is not installed comm...

Отзывы: