Failure: 

If an error on the internal smoke detector 

circuit occurs or when the smoke detector 

is removed, the yellow system error LED 

is lit and smoke alarm, service alarm 

and system error alarm relays are de-

energized.

Low air flow: 

The yellow Low-Flow LED is lit (and the 

relay is de-energized), when the air speed 

in the duct is low or if the UG-5 is installed 

in an inexpedient position on the duct or if 

the UG-5 is very dirty. To make sure that 

the smoke detection function is working, 

apply smoke (i.e. from a smoke machine) 

into the duct to check that the UG-5 is 

indicating a smoke alarm.

DIMENSIONS

(mm)

WIRING DIAGRAM

The relay outputs are shown in power off/alarm condition.

* Not to be used due to changed EMC regulations.

UG-5-AFR-230V UNIGUARD SUPERFLOW STAND-ALONE-UNIT

Optical smoke detector with service alarm, for duct installation.

Electronic air-flow indication.

BASIC PRINCIPLES FOR POSITIONING

For the airflow through the adaptor to be representative of the 

airflow in the ventilation duct, install the detector at a place 

where flow meters etc. normally are mounted, please see our 

installation instructions.

You can also use your national or local rules for mountage 

according to "Methods for measuring airflow in ventilation 

systems".

INSTALLATION

The venturi pipe is made of aluminium and can easily be 

shortened to suit the diameter of the duct. Hole diameter is 

38 mm. For insulated or small circular ducts (100-150 mm) - 

use the mounting bracket, hole diameter is then 51 mm.

MAINTENANCE

The detector contains an intelligent controlling circuit. This 

circuit is adjusting the sensitivity to give an optimal function 

during the whole life time of the detector. When the controlling 

circuit has reached the maximum sensitivity compensation 

for contamination, a service alarm is indicated. This can be 

postponed for a considerable time by cleaning the detector 

once a year with a vacuum cleaner.

AIR FLOW MONITORING

The detector has an electronic air flow monitoring. When the 

detector is correctly installed, the yellow “Low-Flow” LED 

is turned out. The function provides a simple confirmation 

that the air flow from the duct is in fact flowing through the 

housing. It is possible to disable the air flow monitoring in case 

of special installations.

FUNCTION TEST

When the installation is complete, the detector should 

be tested. This can be carried out with smoke or suitable 

testspray, for example RDP-300 (from Calectro). Use the test 

hole on the cover. 

Do not forget to refit the plastic plug after 

test.

NB:

 When installing outdoors or in cold attics etc, where there 

is a risk for condensation, the detector should be insulated 

from the surrounding air with e.g. our weatherproof housing 

UG-COVER-75. In such cases it should be marked with a sign 

"Hidden Detector".

FUNCTION

Normal operation:  In normal operation all relays are  

 energized.

Smoke alarm: 

The LED of the detector is showing  

  red light.

Reset: 

Press the reset button to reset the 

  detector into normal operation.

Service alarm:  

When the detector is sensing smoke or 

is dirty the LED of the detector will first 

show green colour before going into 

alarm with red light. If the detector is 

dirty, it will show green light. This is an 

optical indication (a pre-alarm or  service-

alarm) which means that the detector is 

contaminated and if it is not cleaned, it will 

give a false alarm later on.

195

241

68

Contamination

Jumper ON disables

air flow monitoring

Air flow alarm

Failure

Smoke alarm

Smoke alarm

Test/Reset*

Test/Reset*

230V AC

230V AC
230V AC
230V AC

6

7

A

8

A

3

4

5

1

2

9

A

7

B

8

B

9

B

10

11

12

13

14

15

Verschmutzung

Luftstromalarm

Systemstörung

Rauchalarm

Rauchalarm

Test/Reset*

Test/Reset*

230 V AC

230 V AC
230 V AC
230 V AC

6

7

A

8

A

3

4

5

1

2

9

A

7

B

8

B

9

B

10

11

12

13

14

15

Отзывы: