Failure: 

If there is something wrong with the 

 

detector, the alarm relay will change 

 contacts:

 

a) When the detector module is removed

 

b) When the supply voltage is interrupted

DIMENSIONS

(mm)

WIRING DIAGRAM

Alarm relay:
TWO changing contacts, max 250V, 5A, each.

The relay outputs are shown in normal operation/power on 
condition.

Alarm

output

Service

alarm

output

NO

NC

C

NC

C

6

7

8

Alarm

output

NO

3

4

5

NC

C

Supply 24 VADC (±10%) 

1

2

9

10

UG-3-A4O UNIGUARD SUPERFLOW STAND-ALONE-UNIT 24V

Optical smoke detector with service alarm for duct installation.

BASIC PRINCIPLES FOR POSITIONING

For the airflow through the adaptor to be representative of the 
airflow in the ventilation duct, install the detector at a place 
where flow meters etc. normally are mounted, please see our 
installation instructions.
You can also use your national or local rules for mountage 
according to "Methods for measuring airflow in ventilation 
systems".

INSTALLATION

The venturi pipe is made of aluminium and can easily be 
shortened to suit the diameter of the duct. Hole diameter is 38 
mm. For insulated or circular ducts - use the mounting bracket,  
hole diameter is then 51 mm.

MAINTAINANCE

When the detector becomes contaminated, sensitivity is 
increased, triggering the service alarm. This can be avoided 
for a considerable time by cleaning the detector once a year 
with a vacuum cleaner.

AIR FLOW MONITORING

The detector is fitted with a red plastic switch tongue. When the 
detector is correctly installed, the tongue is bent outwards by 
the air flow. The switch tongue provides a simple confirmation 
that there is no leakage and that the air flow from the duct is in 
fact flowing through the housing.

FUNCTION TEST

When installation is complete, the detector should be tested. 
This can be carried out with smoke or suitable aerosol 
testspray.

NB:

 When installing outdoors or in cold attics etc., where there 

is a risk for condensation, the detector should be insulated 
from the surrounding air with e.g. our weatherproof housing 
UG-COVER.  In  such  cases  it  should  be  marked  with  a  sign 
"Hidden Detector".

FUNCTION

Normal operation: 

In normal operation the alarm relay 

 

is energized, and the relay contacts 

 

are closed between C and NC.

Smoke alarm: 

The LED of the detector is showing 

 

red light and the relay contacts are 

 

changing to C and NO.

Reset: 

Press the reset button to reset the

 

detector into normal operation.

Service alarm:  

When the detector is sensing smoke or
is dirty the LED of the detector will first 
show green colour before going into 
alarm with red light. If the detector is 
dirty, it will show green light. This is 
an optical indication (a pre-alarm or 
 service-alarm) which means that the 
detector is contaminated and if it is not 
cleaned, it will give a false alarm later on.

150

146

180

27

85

154

35