Phone: +46 31-69 53 00 Fax: +46 31-29 32 91 [email protected] www.calectro.se
25
Alarm delay
0-10min
RW
26
DI1 setpoint
0Pa to 2000Pa
RW
27
DI2 setpoint
0Pa to 2000Pa
RW
28
DI1 function
1-2(*5)
RW
29
DI2 function
1-2(*5)
RW
30
Override DAC from
MODBUS
0,1
RW
31
Override DAC value
0-10V(*1,6)
RW
32
Override relay from
MODBUS
0,1
RW
33
Override relay value
0,1(*9)
RW
34
Calibration value
-100Pa to 2000PA
R
35-44
FIFO Alarm log
0-9(*7)
R
(*1) Value is multiplied with 10.
(*2) Operation mode
1. Regulator
mode
2. Pressure sensor -50Pa to +50Pa
3. Pressure sensor 0Pa to 100Pa
4. Pressure sensor 0Pa to 150Pa
5. Pressure sensor 0Pa to 300Pa
6. Pressure sensor 0Pa to 500Pa
7. Pressure sensor 0Pa to 1000Pa
8. Pressure sensor 0Pa to 1600Pa
9. Pressure sensor 0Pa to 2000Pa
(*3) Mean operation mode
1. Regulation on direct pressure value
2. 1.28 sec. mean value
3. 2.56 sec. mean value
(*4) Temperature sensor type
1. CALAIR-PR-NTC
2. Pt1000
3. Temperature from MODBUS
4. NONE/OFF
(*5) Digital input operation
1. Motor alarm function
2. Force setpoint (DI1/DI2 setpoint)
(*6) Register 30 (Override DAC from MODBUS)
must be set to ‘1’
(*7) FIFO Alarm log (latest alarm on register 44)
0. No
alarm
1. High pressure alarm
2. Low pressure alarm
3. DI1 motor alarm
4. DI2 motor alarm
5. Temperature sensor error alarm
(*8) Alarm enable
1. Enable
2. Disable
(*9) Register 32 (Override relay from MODBUS)
must be set to ‘1’
Änderungen und Druckfehler vorbehalten.