CAL
-SERIES
25
10.2
TILT INSTALLATION
Refer to Figure 21 & Figure 22, for 25° to 45° tilts. Locate suspension points as described above under
the title “
”. It is important NOT to over
-tilt the heater. Units are certified for
installation up 45°; however, the MAXIMUM recommend tilt is no greater than 25°.
WARNING:
It is the responsibility of the installer to use hanging chain that is a minimum of
2/0 or with a minimum support capacity of no less than 75 lbs. Also make sure all suspension
points are adequate to support weight of heater and any accessories. Also make sure all S-
Hooks are affixed properly and the open ends squeezed closed. If the suspension system fails,
it is the responsibility of the installer. A failed suspension system can cause property damage,
severe injury and/or death.
Refer to page 27
to page 31
.
25° TILT (ALL LENGTHS)
NOTE: 25° Tilt is maximum recommended tilt for most installations.
Figure 21. 25° TILT
Содержание CAL Series
Страница 18: ...CAL SERIES 14 CAL 40A 50A 15 4 16 M Figure 7 CAL 40A 50A 15 4 16 M...
Страница 20: ...CAL SERIES 16 CAL 40A 50A 15 4 16 M THREE PIECE MODEL Figure 9 CAL 40A 50A 15 4 16 M THREE PIECE MODEL...
Страница 21: ...CAL SERIES 17 CAL 40A 50A 75A 20 6 1 M FOUR PIECE MODEL Figure 10 CAL 40A 50A 75A 20 6 1 M FOUR PIECE MODEL...
Страница 23: ...CAL SERIES 19 90 ELBOW PACKAGE Figure 13 90 ELBOW PACKAGE 180 U BEND PACKAGE Figure 14 180 U BEND PACKAGE...
Страница 37: ...CAL SERIES 33 90 ELBOW KIT Figure 29 90 ELBOW KIT INSTALLATION 180 U BEND KIT Figure 30 180 U Bend Kit...
Страница 63: ...CAL SERIES 59 24 0 GAS VALVES Figure 47 GAS VALVE...
Страница 83: ...CAL SERIES 79...