MANIFOLD PRESSURE REGULATOR ADJUSTMENT AND PRESSURE VERIFICATION
PROCEDURE:
WARNING
INSTALLER MUST VERIFY AND ADJUST, IF NECESSARY, THE MANIFOLD OPERATING PRESSURE OF THIS HEATER
ACCORDING TO THE INSTALLATION MANUAL AND RATING PLATE OF THIS HEATER.
FAILURE TO DO SO WILL VOID ALL WARRANTIES AND MAY CAUSE DAMAGE, INJURY AND/OR DEATH.
IF YOU HAVE ANY QUESTIONS CONCERNING THESE INSTRUCTIONS, CALL CALCANA AT 800-778-6729 BEFORE YOU
VERIFY AND/OR ADJUST THE MANIFOLD FUEL PRESSURE ON THE HEATER.
No one should work on or install this heater
unless they are a licensed/qualified and insured contractor trained in the appropriate trade or technical fields
(Gasfitting-HVAC-Electrician) related to the installation and/or service of this heater.
Person(s) who service and/or install this unit accept full liability and responsibility for its operation.
TOOLS REQUIRED
-Small Flat Blade Screw Driver
-2 mm (millimeter) allen wrench
-3 mm (millimeter) allen wrench
-Manometer that measures i
nches of water column (“ W.C.)
-Volt Meter capable of reading AC and DC voltage in a range of 0 to at least 30 volts
INITIAL STEPS:
1)
The installer must verify that the heater being installed is of the correct fuel type for the available fuel
that is supplied for this installation. This includes any high altitude correction that may be applicable
for your installation. Confirm site has adequate fuel supply to operate all gas fired appliances,
including this/these heater(s), at their maximum rated capacity simultaneously (at the same time).
Make sure gas lines and pressure regulators are of a capacity to deliver the correct line pressure within
the specified range for your fuel type (5” to 14” w.c. for natural gas and 12” to 14” w.c. for propane
or Propane
fuel) to the heater’s gas line inlet connection, with all gas fired appliances on site operating
at the same time. If you are unable to achieve the stated line pressures during operation, you will not
be able to verify and/or adjust the gas manifold pressure setting on this heater, and the heater will
not operate correctly. If fuel pressure is too low, the heater will not have enough fuel to achieve its
maximum heat level. Alternatively, if the fuel line pressure is too high, the valve can be damaged.
2)
Make sure all gas-fired appliances on site, other than this heater, are on and operating at the same
time. Otherwise, an inaccurate reading of manifold pressure may occur.
3)
Make sure this heater is not operating and is turned off when you start this procedure.
4)
START BY
opening the service door and identifying the location of the gas valve and the modulator.
Remove the black plastic cap from the adjustment tower.
Содержание CAL Series
Страница 18: ...CAL SERIES 14 CAL 40A 50A 15 4 16 M Figure 7 CAL 40A 50A 15 4 16 M...
Страница 20: ...CAL SERIES 16 CAL 40A 50A 15 4 16 M THREE PIECE MODEL Figure 9 CAL 40A 50A 15 4 16 M THREE PIECE MODEL...
Страница 21: ...CAL SERIES 17 CAL 40A 50A 75A 20 6 1 M FOUR PIECE MODEL Figure 10 CAL 40A 50A 75A 20 6 1 M FOUR PIECE MODEL...
Страница 23: ...CAL SERIES 19 90 ELBOW PACKAGE Figure 13 90 ELBOW PACKAGE 180 U BEND PACKAGE Figure 14 180 U BEND PACKAGE...
Страница 37: ...CAL SERIES 33 90 ELBOW KIT Figure 29 90 ELBOW KIT INSTALLATION 180 U BEND KIT Figure 30 180 U Bend Kit...
Страница 63: ...CAL SERIES 59 24 0 GAS VALVES Figure 47 GAS VALVE...
Страница 83: ...CAL SERIES 79...