background image

 

FREETIME 

® - 

HEXAMOTION 

®

 

High Efficiency Recovery Unit 

OPERATING AND COMMISSIONING INSTRUCTIONS

 

 

MS-CDF-010 

Ind  F 

Maj. 18/05/2017 

Créé par : JC 

Validé par : AR 

Page 11/57 

 

o

 

Clock (HS - 1/1) is not activated (normal speed timer) 

o

 

Clock (LS - 1/2) is activated (reduced speed Timer) 

o

 

External operation (HS - 1/1) and external stop are not activated. 

o

 

 

III.4. COMPOSITION  

III.4.a.  FREETIME

®

 

 

 
Nom 

Détails 

IPC 

Padlockable switch 

VS 

Supply air fan 

VR 

Extract air fan 

CO2* 

CO2 sensor (DIVA

®

-QUATTRO

®

 only) 

SEG* 

Outdoor temperature sensor 

SRG* 

Extract temperature sensor 

SSG* 

Supply temperature sensor 

FS 

Supply filter 

FR 

Extract filter  

DEPS / TRPS 

Supply pressure switch or supply pressure transmitter for version LOBBY

®

-MAC2

®

-QUATTRO

®

 

THA* 

External fros guard (version PREMIUM BC) 

THS* 

Overheat security thermostat (version PREMIUM BE) 

BC/BE* 

Hot water coil or electrical battery (see version)  

ROUE 

Rotative exhanger with rotative sentinel included 

*components non included in SEASON version 
 
 
 
 
 
 
 
 
 
 
 

Содержание Freetime 1500

Страница 1: ...FREETIME HEXAMOTION High Efficiency Recovery Unit OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 010 Ind F Maj 18 05 2017 Cr par JC Valid par AR Page 1 57 FREETIME HEXAMOTION...

Страница 2: ...ON 05 08 10 III 3 f QUATTRO impossible with version FREETIME 500 800 et HEXAMOTION 05 08 10 III 4 COMPOSITION 11 III 4 a FREETIME 11 III 4 b HEXAMOTION FIRST PREMIUM 12 III 4 c HEXAMOTION SEASON 13 II...

Страница 3: ...HS 33 V 4 c Temperature setpoint modification 34 V 4 d Forced stop of the unit or forced start LS or HS on the remote control 34 V 4 e Choice of language 34 V 5 Intermediate settings service level 34...

Страница 4: ...hould be installed only by a technical person qualified for this type of work Use the required personal protection devices so as to avoid injuries caused by electrical and mechanical hazards injuries...

Страница 5: ...on solution or a place of deposit for the product Contacts for pick up requests E mail operations pro ecologic france com Phone 01 30 57 79 14 Internet www e dechet com II INSTALLATION II 1 Handling T...

Страница 6: ...nds that should be properly stretched Install the unit such that bad weather or ambient temperature cannot damage the internal items of the unit during installation as well as when used later Provide...

Страница 7: ...COMMISSIONING INSTRUCTIONS MS CDF 010 Ind F Maj 18 05 2017 Cr par JC Valid par AR Page 7 57 HEXAMOTION 60 80 Fasten the assembly tabs at the rear of the CTA M8 screw nut Disassemble the central panel...

Страница 8: ...High Efficiency Recovery Unit OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 010 Ind F Maj 18 05 2017 Cr par JC Valid par AR Page 8 57 Version FIRST PREMIUM Version SEASON Connect the connectors bet...

Страница 9: ...d battery If required it can also manage a non integrated cold water battery HEXAMOTION PREMIUM BE Econological management of the fans rotative exchanger and an electrical integrated battery If requir...

Страница 10: ...speed timer o Clock LS 1 2 is activated reduced speed Timer o External operation HS 1 1 and external stop are not activated III 3 d LOBBY Constant pressure ventilation Pa CONSTANT PA MODE Constant pre...

Страница 11: ...ils IPC Padlockable switch VS Supply air fan VR Extract air fan CO2 CO2 sensor DIVA QUATTRO only SEG Outdoor temperature sensor SRG Extract temperature sensor SSG Supply temperature sensor FS Supply f...

Страница 12: ...HEXAMOTION High Efficiency Recovery Unit OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 010 Ind F Maj 18 05 2017 Cr par JC Valid par AR Page 12 57 III 4 b HEXAMOTION FIRST PREMIUM 05 45 60 80 FS1 FS2...

Страница 13: ...switch or extract pressure transmitter for version LOBBY MAC2 QUATTRO THA External fros guard version PREMIUM CO THS Overheat security thermostat version PREMIUM BE BC BE DXR Hot water coil or electr...

Страница 14: ...EASON Nom D tails DEPFS Filter pressure switch DEPS ou TRPS Extract pressure switch or extract pressure transmitter for version LOBBY MAC2 QUATTRO TRAFO Transformer 230 24V K1 Contactor of electric ba...

Страница 15: ...S Supply pressure switch or extract pressure transmitter for version LOBBY MAC2 QUATTRO DEPR ou TRPR Extract pressure switch or extract pressure transmitter for version LOBBY MAC2 QUATTRO 05 45 only T...

Страница 16: ...OTION High Efficiency Recovery Unit OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 010 Ind F Maj 18 05 2017 Cr par JC Valid par AR Page 16 57 IV ELECTRIC WIRING IV 1 POWER SUPPLY IV 1 a FREETIME IV 1...

Страница 17: ...FREETIME HEXAMOTION High Efficiency Recovery Unit OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 010 Ind F Maj 18 05 2017 Cr par JC Valid par AR Page 17 57 IV 2 RACCORDEMENT SEASON...

Страница 18: ...IME Except SEASON D signation Bornes Raccordement ADP shunted if not used 1 2 Connect on fire emergency stop free voltage NC contact DAD shunted if not used 3 4 Connect on DAD smoke detector default c...

Страница 19: ...tional LOBBY EC for opening dampers during Night Cooling pay attention 24V 2A Max to relay TRPS 23 Agnd UI1 Connect to supply Pressure Transmitter see chapter IV 8 DEPS 24 UI1 Connect to terminal 1 an...

Страница 20: ...justable The rotative exchanger stops to bring directly outside fresh air IV 5 b Version FIRST PREMIUM Rotative exchanger is factory wired CORRIGO controller drives automatically the bypass thanks to...

Страница 21: ...FREETIME HEXAMOTION High Efficiency Recovery Unit OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 010 Ind F Maj 18 05 2017 Cr par JC Valid par AR Page 21 57...

Страница 22: ...par AR Page 22 57 IV 6 Filters pressure switches wiring and connection Le pressostat filtre air neuf est c bl et raccord d usine IV 7 Fan pressure switch wiring and connection Les pressostats ventila...

Страница 23: ...esh air At the end of Night Cooling period heating is blocked to 0V during 60 minutes Start conditions customizable in chapter V 5 b 2 o Outside temperatures are higher to 22 C during the day o Clocks...

Страница 24: ...on 24V G of the 3 ways valve actuator Terminal 29 on 0V G0 of the 3 ways valve actuator Terminal 30 on 10V Y of the 3 ways valve actuator Connect NC contact C and 2 of THA Deicing Thermostat on 5 and...

Страница 25: ...rive the direct expansion battery module Attention 24V 2A Max to relay o 0 10V output to connect to 29 and 30 terminals 29 0V et 30 0 10V ATTENTION In case of a 24V output is used make a relay between...

Страница 26: ...ill be connected between DI8 terminal of the controller and 13 of the terminal block free voltage contact required IV 16 Dehumidification function See parameters in chapiter V 8 It is possible to asso...

Страница 27: ...pter V 8 You need to use a repeater in case of you want to connect o More than one unit on the same display maximum 6 o A remote control at a distance higher than 100m In this case you can move to 1 k...

Страница 28: ...enus o Up and Down buttons help to increase or decrease the values of a parameter when you have access to Right and left buttons help to navigate inside the parameter o OK button help to enter the val...

Страница 29: ...used ATTENTION Do not modify parameters which are not in bold characters in this case no after sales will be admitted Regulation mode Year month day Hour System state of unit SP Setpoint T C Act T C...

Страница 30: ...nalogue Input DI Digitale input UI Universel Input AO Analogue output AI1 T AS suuply AI2 T Ext outdoor AI3 T AR extract AI4 DI1 Al Filter1 DI2 Over heat ou External frost guard DI3 Ext 1 2 DI4 Ext 1...

Страница 31: ...V 4 b Frequency control manuel vent EAF Output 1 1 180Pa 5 Output 1 2 180Pa 5 Frequency control ECO OU DIVA manuel vent SAF Output 70 5 or Pressure Control EAF LOBBY Real 183Pa exemple Setpoint 180 Pa...

Страница 32: ...y 2 Per 1 06 00 22 00 Per 2 00 00 00 00 Etc untill sunday holidays Timer reduced speed Slow speed Monday 2 Per 1 06 00 22 00 Per 2 00 00 00 00 Slow speed Monday Friday 2 Per 1 06 00 22 00 Per 2 00 00...

Страница 33: ...d password 3333 required Access Hour settings holidays System is set with no vacation time If you need to reduce functionnement time during vacation time set the functionning time window as indicated...

Страница 34: ...2 or HS 7 manual speed 1 1 In standard unit works automatically with clocks 7 Auto If unit do not work in automatic mode an alarm will start Manual speed 1 1 and manual speed 1 2 modes must be used o...

Страница 35: ...ht cooling speed is set in standard in 85 You can modify it You can also change the temperature of Night Cooling activation outside temperature day and deactivate it V 6 c CO2 setpoint for DIVA QUATTR...

Страница 36: ...urrent level ADMIN Configuration Communication Syst me Port 1 Esclave 1 et 2 Activation MODBUS RS485 and settings see chapter V 8 3 et 4 Activation BACNET MSTP and settings see chapter V 8 5 et 6 Sett...

Страница 37: ...Read Input registers 4 Write single Coils 5 Write single register 6 Write multiple Coils 15 Write multiple register 16 EXOL Type R Real 3 3E38 3 3E38 I Integer 32768 32767 X Index 0 255 L Logic 0 1 T...

Страница 38: ...ault settings 47808 MAC The MAC address of the device This need to be unique only to the subnet Device ID The ID of a device used to identify it on the BACnet network This number cannot be duplicated...

Страница 39: ...found To solve a default press the alarm button red delete then enter the default with directional arrows and press OK button Attention do not block Description Cause CORRIGO screen do not light up Un...

Страница 40: ...xhaust temperature is higher than 50 C 2 Temperature setting is too high 3 Exhaust fan is stopped vent AS Default when hot battery is in full capacity 23 Electric heating is overheated Ext DI3 must be...

Страница 41: ...V signal is inverted Pressure transmittor on intake air is short circuited 59 CO2 sensor error Control the Value on Ext AI4 A 5s 0 10V signal is inverted CO2 transmittor is in short circuit 85 in manu...

Страница 42: ...odicity of the cleaning Componants 1 MONTH 3 MONTHS 6 MONTHS 12 MONTHS Filtration Blowing for the G4filters Cleaning for the G4filters Washing for the G4filters Replacement Of the filters if needed Ro...

Страница 43: ...OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 010 Ind F Maj 18 05 2017 Cr par JC Valid par AR Page 43 57 Take the battery and remove it softly Press firmly the new battery in the support Note Atten...

Страница 44: ...FREETIME HEXAMOTION High Efficiency Recovery Unit OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 010 Ind F Maj 18 05 2017 Cr par JC Valid par AR Page 44 57 ANNEXES Command diagram...

Страница 45: ...ME HEXAMOTION High Efficiency Recovery Unit OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 010 Ind F Maj 18 05 2017 Cr par JC Valid par AR Page 45 57 VII 3 Motors diagrams FREETIME 500 800 HEXAMOTION...

Страница 46: ...ETIME HEXAMOTION High Efficiency Recovery Unit OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 010 Ind F Maj 18 05 2017 Cr par JC Valid par AR Page 46 57 VII 4 Motors diagrams FREETIME 1500 HEXAMOTION...

Страница 47: ...ETIME HEXAMOTION High Efficiency Recovery Unit OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 010 Ind F Maj 18 05 2017 Cr par JC Valid par AR Page 47 57 VII 5 Motors diagrams FREETIME 2000 HEXAMOTION...

Страница 48: ...E HEXAMOTION High Efficiency Recovery Unit OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 010 Ind F Maj 18 05 2017 Cr par JC Valid par AR Page 48 57 VII 6 Motors diagrams FREETIME 2700 3500 HEXAMOTIO...

Страница 49: ...TIME FREETIME 500 0 200 400 600 800 150 250 350 450 550 650 D bit m3 h Pression statique Pa 100 90 80 70 60 50 40 FREETIME 800 0 100 200 300 400 500 600 700 200 300 400 500 600 700 800 900 D bit m 3 h...

Страница 50: ...300 400 500 600 700 800 600 800 1000 1200 1400 1600 1800 2000 2200 D bit m 3 h Pression statique Pa 100 90 80 70 60 50 40 FREETIME 2700 0 200 400 600 800 600 1000 1400 1800 2200 2600 3000 3400 D bit...

Страница 51: ...FREETIME HEXAMOTION High Efficiency Recovery Unit OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 010 Ind F Maj 18 05 2017 Cr par JC Valid par AR Page 51 57 VII 7 b HEXAMOTION...

Страница 52: ...FREETIME HEXAMOTION High Efficiency Recovery Unit OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 010 Ind F Maj 18 05 2017 Cr par JC Valid par AR Page 52 57...

Страница 53: ...FREETIME HEXAMOTION High Efficiency Recovery Unit OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 010 Ind F Maj 18 05 2017 Cr par JC Valid par AR Page 53 57...

Страница 54: ...tart normal speed 6 In operation 9 CO2 functionning 10 Night cooling 12 stopped X 3 MSV 40003 Outdoor Temperature R 1 AV 40001 Operating time of the supply fan R 4 AV 40004 Operating time of the extra...

Страница 55: ...t for T C out de 10 C R 16 18 Supply setpoint Set in constant supply comp ext for T C out de 15 C R 17 18 Return setpoint Set in return control R 18 AV 30018 21 speed supply HS setpoint In for ECO and...

Страница 56: ...f 1 ALARM L 30 BV 20030 SAF default If 1 ALARM L 33 BV 20033 EAF default If 1 ALARM L 34 BV 20034 Filter default If 1 ALARM L 38 BV 20038 Antifreeze default If 1 ALARM L 40 BV 20040 Fire default If 1...

Страница 57: ...FREETIME HEXAMOTION High Efficiency Recovery Unit OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 010 Ind F Maj 18 05 2017 Cr par JC Valid par AR Page 57 57 VIII NOTES...

Отзывы: