XXIV.3.
Alarm status (read-only)
It is not possible to acknowledge alarms (class A and B) via communication.
Read
Write
Modbus
Register Type
Modbus
Address
Modbus
Variable
BACnet
Address
Details
Alarm presence
X
Input Status
30
bool
BV, 20030 0=no alarm / 1=at least one alarm is present
Supply air fan fault
X
Input Status
33
bool
BV, 20033 0=no alarm / 1=alarm presence
Extract air fan fault
X
Input Status
34
bool
BV, 20034 0=no alarm / 1=alarm presence
Supply / extract air filters fault
X
Input Status
38
bool
BV, 20038 0=no alarm / 1=alarm presence
Internal battery fault
X
Input Status
80
bool
BV, 20080 0=no alarm / 1=alarm presence
Electrical heating coil overheating
X
Input Status
55
bool
BV, 20055
0=no alarm / 1=alarm presence
Only for units with electrical heating coil
hot water heating coil frost protection
X
Input Status
40
bool
BV, 20040
0=no alarme / 1=alarm presence
Only for units with hot water heating coil
Fire mode active
X
Input Status
42
bool
BV, 20042 0=no alarm / 1=alarm presence
Содержание EVERSKY 500
Страница 43: ...EVERSKY MS CDF 019 Manufacturing Nr 220001 Version B Update 2022 06 14 43 70 Supply fan Extract fan...
Страница 48: ...EVERSKY MS CDF 019 Manufacturing Nr 220001 Version B Update 2022 06 14 48 70 XVII GENERAL WIRING DIAGRAM...
Страница 49: ...EVERSKY MS CDF 019 Manufacturing Nr 220001 Version B Update 2022 06 14 49 70...
Страница 69: ...EVERSKY MS CDF 019 Manufacturing Nr 220001 Version B Update 2022 06 14 69 70 NOTES Date Stakeholder Comments...
Страница 70: ...EVERSKY MS CDF 019 Manufacturing Nr 220001 Version B Update 2022 06 14 70 70 Date Stakeholder Comments...