background image

 

DIABLO

®

 - DIABLO TWIN

® 

F400-120 

SMOKE AND HEAT EXHAUST FAN 

 

 

2015/03 

 

Page : 6 

 

 

IV.3 / DIABLO TWIN (KED TWIN)outdoor kit

 

 
 

 

V.3 /  Optionnal electric accessories

 

 

For optionnal electric accessories (Dahlander, separated coils, control box) refer to their manuals. 

 

 

V.3.a / Control box 

 

Control box (

CDF

) can be mounted directly on DIABLO

® 

DIABLO TWIN

®

 

 

The 2 motors of DIABLO TWIN

®

 can be controlled with one control box. In this case check that it can       

hold with the intensity of the 2 motors. 

 

V.3.b / Speed variation with frequency convertor 

 

 

The speed of the motors can be  modified with frequency convertor only on variable comfort. 

  The speed variation is not possible in smoke exhaust  running. 
Convertors are mounted under motor covers for outdoor installation or on the motor support in standard. This 
configuration has  F400-120 certification. 

 

When only using in variable comfort  ( electric connection without logic 400-120 control box), speed 

variation can be done with VFT or VFM  frequency convertor.  

 

When using in variable comfort and smoke exhaust ( electric connection with a logic 400-120 control 

box), speed variation can only be done with VFT or VFM  frequency convertor.  

 

Speed  variation is only possible with  1 speed motors (4,6 or 8 poles), of a power higher or equal to  

0,37kW. 

 

The 2 motors of DIABLO TWIN

®

 can be controlled with one frequency convertor . 

In this case you need to oversize frequency convertor of 1 size. Ex : 2 x 0,37kW = 1,1 Kw. 

 

DIABLO TWIN Outdoor kit  mounted in standard 
includes: 

• 

A roof in 3 pieces (mounted) 

• 

Two motor covers (monted) 

• 

Two rain visors with grill on discharge (to be 
mounted on site) 

Rain visor must be mounted with provided screws as 
seen on the drawing: 

Содержание Diablo F400-120

Страница 1: ...DIABLO DIABLO TWIN F400 120 SMOKE AND HEAT EXHAUST FAN OPERATING AND COMMISSIONING MANUAL 2015 03 1 ...

Страница 2: ...All accessories are present dampers roof electric switchgear etc After unpacking the equipment the waste must be disposed of in compliance with the current standards No packaging should be discarded into the environment I 3 Storing The equipment must be stored in shade in a dry place at a temperature between 20 C and 40 C II INSTALLATION II 1 Handling The units must only be moved in their installa...

Страница 3: ...ries BEFORE SWITCHING ON THE DIABLO PAY ATTENTION THAT ALL THE SCREWS ARE WELL TIGHTENED IN PARTICULAR THE ROTATING COMPONENTS III ELECTRIC WIRING OF THE 3 PHASE MOTOR Electric connection will be done on the padlockable switch or on the optionnal control box mounted on the DIABLO DIABLO TWIN In this case refer to the manual with control box 1 Speed 2 tensions Star Delta connexions 230V 400V 4 6 8 ...

Страница 4: ... 1 tension Separated coils 400V 4 6 et 6 8 poles Safety switch III 2 2 speeds motor Dahlander III 3 2 Speeds motor Separated coils High speed Low speed 2 4 6 1 3 5 2 4 6 1 3 5 L1 L2 L3 2 4 6 1 3 5 2 4 6 1 3 5 L1 L2 L3 2U 2V 2W 1U 1V 1W 2U 2V 2W 1U 1V 1W 2 4 6 1 3 5 2 4 6 1 3 5 L1 L2 L3 2 4 6 1 3 5 2 4 6 1 3 5 L1 L2 L3 2U1 2V1 2W1 1U1 1V1 1W1 2U1 2V1 2W1 1U1 1V1 1W1 ...

Страница 5: ...r which must be the same as written on the mo tor plate In case of overcurrent stop the unit and contacte your retailer IV 2 Fan When wiring is finished check the direction of rotation of the fan reverse 2 of the phases on the motor to invert the direction of rotation NOTA a fan that does not rotate in the right sens do not have an apposite airflow but an airflow lower than forecasted An extended ...

Страница 6: ...llation or on the motor support in standard This configuration has F400 120 certification When only using in variable comfort electric connection without logic 400 120 control box speed variation can be done with VFT or VFM frequency convertor When using in variable comfort and smoke exhaust electric connection with a logic 400 120 control box speed variation can only be done with VFT or VFM frequ...

Страница 7: ...he fan box Check the ducts VI 2 Fans Dust the wheel if necessary Fill in the service manual below everytime an intervention is done on DIABLO DIABLO TWIN box Before to start any intervention you must electrically insulate the box with padlockable switch IPC on OFF position Date intervention Comments ...

Страница 8: ...in the turbine Anti vibration moutings or fan chassis is broken Wrong direction of motor rotation Clean the wheel Replace anti vibration mountings Reverse 2 phases on motor Wrong airflow Wrong direction of motor rotation Wrong estimation of pressure drop in the duct network Reverse 2 phases on motor Modify duct network or contact us DIABLO DIABLO TWIN F400 120 SMOKE AND HEAT EXHAUST FAN 2015 03 Pa...

Отзывы: