IV / COMPONENTS 

 

 

IV.1 / Motor 

 

 

- The electrical conduits of the smoke exhaust fan do not need protection against overloads but only magnetic , in 

accordance with  norm ref NFC15-100 , they must be dimensionned with highest overloads that motor can  stand. Power 
supply must be provided by heat-resistant cables 

CR1. 

Inside the rooms cables must be resistant enough to ensure good functionning of the DIABLO during smoke exhaust. 

 

- Check the tension of the grid which must be the same as written on the moteur plate 

 

- If the diablo is used in confort , connect PTO if they are on the motor. 

 

- When starting the unit , check the absorbed intensity of the motor which must be the same as written on the mo-

tor plate. In case of overcurrent stop the unit and contacte your retailer. 

 

IV.2 / Fan

 

 

When wiring is finished, 

check  the  direction  of  rotation  of  the  fan   

(reverse  2 of the phases on the motor  to 

invert the direction of rotation). 
 

NOTA 

: a fan that does not rotate in the right sens do not have an apposite airflow but an airflow lower than forecasted 

An extended use on of the fan rotating in the wrong direction may produce vibrations and dammage motor bearings. 

 

 

 

ATTENTION  :  For  2  speeds  motor  check  that  motor  turns  in  the 
same direction in high and low speed. 

 

DIABLO

®

 - DIABLO TWIN

® 

F400-120 

SMOKE AND HEAT EXHAUST FAN 

 

 

2015/03 

 

Page : 5 

 

V / ACCESSORIES 

 

 

IV.2 / DIABLO Outdoor Kit  (KED)

 

 

 

 

The DIABLO outdoor kit supplied as standard equipment 
includes: 
 

 

Roof

 

• 

Motor cover (mounted) 

• 

Rain visor with grill on discharge 

Содержание Diablo F400-120

Страница 1: ...DIABLO DIABLO TWIN F400 120 SMOKE AND HEAT EXHAUST FAN OPERATING AND COMMISSIONING MANUAL 2015 03 1 ...

Страница 2: ...All accessories are present dampers roof electric switchgear etc After unpacking the equipment the waste must be disposed of in compliance with the current standards No packaging should be discarded into the environment I 3 Storing The equipment must be stored in shade in a dry place at a temperature between 20 C and 40 C II INSTALLATION II 1 Handling The units must only be moved in their installa...

Страница 3: ...ries BEFORE SWITCHING ON THE DIABLO PAY ATTENTION THAT ALL THE SCREWS ARE WELL TIGHTENED IN PARTICULAR THE ROTATING COMPONENTS III ELECTRIC WIRING OF THE 3 PHASE MOTOR Electric connection will be done on the padlockable switch or on the optionnal control box mounted on the DIABLO DIABLO TWIN In this case refer to the manual with control box 1 Speed 2 tensions Star Delta connexions 230V 400V 4 6 8 ...

Страница 4: ... 1 tension Separated coils 400V 4 6 et 6 8 poles Safety switch III 2 2 speeds motor Dahlander III 3 2 Speeds motor Separated coils High speed Low speed 2 4 6 1 3 5 2 4 6 1 3 5 L1 L2 L3 2 4 6 1 3 5 2 4 6 1 3 5 L1 L2 L3 2U 2V 2W 1U 1V 1W 2U 2V 2W 1U 1V 1W 2 4 6 1 3 5 2 4 6 1 3 5 L1 L2 L3 2 4 6 1 3 5 2 4 6 1 3 5 L1 L2 L3 2U1 2V1 2W1 1U1 1V1 1W1 2U1 2V1 2W1 1U1 1V1 1W1 ...

Страница 5: ...r which must be the same as written on the mo tor plate In case of overcurrent stop the unit and contacte your retailer IV 2 Fan When wiring is finished check the direction of rotation of the fan reverse 2 of the phases on the motor to invert the direction of rotation NOTA a fan that does not rotate in the right sens do not have an apposite airflow but an airflow lower than forecasted An extended ...

Страница 6: ...llation or on the motor support in standard This configuration has F400 120 certification When only using in variable comfort electric connection without logic 400 120 control box speed variation can be done with VFT or VFM frequency convertor When using in variable comfort and smoke exhaust electric connection with a logic 400 120 control box speed variation can only be done with VFT or VFM frequ...

Страница 7: ...he fan box Check the ducts VI 2 Fans Dust the wheel if necessary Fill in the service manual below everytime an intervention is done on DIABLO DIABLO TWIN box Before to start any intervention you must electrically insulate the box with padlockable switch IPC on OFF position Date intervention Comments ...

Страница 8: ...in the turbine Anti vibration moutings or fan chassis is broken Wrong direction of motor rotation Clean the wheel Replace anti vibration mountings Reverse 2 phases on motor Wrong airflow Wrong direction of motor rotation Wrong estimation of pressure drop in the duct network Reverse 2 phases on motor Modify duct network or contact us DIABLO DIABLO TWIN F400 120 SMOKE AND HEAT EXHAUST FAN 2015 03 Pa...

Отзывы: