background image

19

Plumbing Connections

IMPORTANT!  Always  check  local  codes  prior  to  any  in-ground  spa 

installation. 
Once the spa and equipment are properly located, you will want to lay out 

the plumbing run.
Trenches should be deep and wide enough to allow all pipes to be buried 

below the frost line and should be in as straight a line from the spa to the 

equipment as possible. Check local code requirements for underground 

pipes. Always know what is under the ground before you dig anywhere.

You will need 2” flex or PVC lines for your suction, intake, and air line. In 

ground spas have marked intake and suction lines, making it easy find and 

connect to and from the spa and equipment pack.
The  plumbing  run  should  not  be  any  longer  than  15  feet  to  maximize 

water  pressure. Another  way  to  maximize  water  pressure  is  to  limit  (or 

even eliminate) the use of 90˚ elbows in your plumbing run. A more direct 

plumbing run using 45˚ elbows is more efficient, and promotes increased 

water pressure.

Identifying Plumbing Lines

The spa’s plumbing lines are clearly marked during water testing at the 

factory. This is done to assist installers in properly identifying the installation. 

We still recommend that the installers verify plumbing lines prior to gluing. 

This can be done by using one of the following techniques. 

Air Test

The  air  test  requires  a  wet/dry  vacuum.  Locate  the  plumbing  line  you 

wish to identify and secure the vacuum hose to cut open end. Turn on the 

vacuum, enter the spa and listen for vacuum suction sound from inside the 

spa side filter canister. If you hear the suction sound in the canister, the 

line is properly marked and can be connected to the suction side of the 

pump on the equipment pack.

Water Test

The  water  test  requires  a  garden  hose  and  water  source.  Locate  the 

plumbing line you wish to identify and secure the outlet side of the garden 

hose to cut open end. Turn on the water supply to the garden hose, enter 

the spa and look for water inside the spa side filter canister. If you see 

water in the canister the line is properly marked and can be connected to 

the suction side of the pump on the equipment pack.
If any plumbing line is not properly marked or not marked at all, follow 

either the air or water test procedure until all lines are identified prior to 

gluing. 

Содержание Avalon A726B

Страница 1: ......

Страница 2: ...ormation and or assistance please contact L M S Customer Service Department 1462 East Ninth Street Pomona CA 91766 Toll Free 1 800 CAL SPAS Fax 1 909 629 3890 www calspas com Contents Pre Delivery and...

Страница 3: ...e responsibility for any performance or warranty issues and may void portions of their warranty as a result For this reason we strongly recommend they hire an experienced professional for their instal...

Страница 4: ...oing this you will have a place to change clothes and not be uncomfortable Consider your privacy In a cold weather climate bare trees won t provide much privacy Think of your spa s surroundings during...

Страница 5: ...n cycles does not make too much noise for spa owners and or neighbors Ensure the equipment can be easily serviced for filter cleaning and periodic inspections in the location chosen If you are using a...

Страница 6: ...ure the structure will support the weight of 150 pounds per square foot To properly identify the weight of your new spa when full remember water weighs 8 33 lbs per gallon For example an average 8 spa...

Страница 7: ...ontact points Be sure not to seal the bottom off and making a sealed box You will need adequate water drainage for escape under the spa A gravel beds around the concrete base will help with this Site...

Страница 8: ...in order to provide an unobstructed passageway to the installation location Plan the Delivery Route Consider the following when planning your delivery route Check the width of gates doors and sidewal...

Страница 9: ...equate preparations Special Circumstances The use of a crane for delivery and installation may become necessary if you are unable to provide an adequate delivery route It is used primarily to avoid in...

Страница 10: ...contractor and approved by a local building electrical inspector GFCI and Wiring Requirements The power supplied to the spa must be on a dedicated GFCI protected circuit as required by ANSI NFPA 70 wi...

Страница 11: ...1 One 50 amp GFCI Service 2 One 30 amp GFCI Service 1 Four 8 AWG copper wires Service 2 Three 8 AWG copper wires Fitness Pro 4700 spa Service 1 swim side One 60 amp GFCI Service 1 Four 8 AWG copper wi...

Страница 12: ...uring the 6300 Control System The 6300 control system requires higher power than other 240V sys tems Dip switch 10 is factory set in the ON position This causes the heater to shut off when any pump is...

Страница 13: ...11 GFCI Wiring Diagram...

Страница 14: ...it before next usage All 120V spas must have a GFCI This can be either a 20 amp GFCI receptacle or a GFCI cord and plug kit as shown at right CKIT110 P N ELE09700086 Testing the GFCI Breaker Test the...

Страница 15: ...ctrical circuit must be installed by an electrical contractor and approved by a local building electrical inspector RCD and Wiring Requirements The power supplied to the spa must be on a dedicated RCD...

Страница 16: ...ce 2 One 32 amp RCD or two 16 amp RCDs Service 2 Three 10 AWG copper wires In Ground Spas Designer in ground spas with one 3 kW heater One 32 amp RCD or two 16 amp RCDs Four 10 AWG copper wires Design...

Страница 17: ...15 RCD Wiring Diagram...

Страница 18: ...16 Installing the In Ground Shell...

Страница 19: ...ow is typical for a system with two pumps with external heater and external filter Designer Spa Specifications DIJ401 DIJ406 Equipment pack weight 250 lbs DIJ407 Equipment pack weight 300 lbs 2 5 HP h...

Страница 20: ...18...

Страница 21: ...ked during water testing at the factory This is done to assist installers in properly identifying the installation We still recommend that the installers verify plumbing lines prior to gluing This can...

Страница 22: ...and below ground installations In most cases the use of flexible PVC plumbing is acceptable when properly buried in trenches Most water plumbing lines are 2 or larger and must be schedule 40 or heavie...

Страница 23: ...ion 3 loom NOTE This connection must be kept dry We recommend that a waterproof junction box be used in installations where moisture could penetrate this terminal connector Lay out the extension loom...

Страница 24: ...h the conduit repeat steps 5 and 6 above In Ground Spa Light Installation Instructions On spas ordered with in ground lights the factory installs the light niche for you The next steps of installation...

Страница 25: ...slack around back of light housing and attach light to 3 niche with mounting screw Cut the cord at the junction box leaving at least 6 15 cm of cord to 4 make connections Strip 6 15 cm of the out cor...

Страница 26: ...24...

Страница 27: ...the coping should be 4 above the surrounding area In either event it is recommended to dig out an area around the spa exposing the flange of the coping and just under it This is important as concrete...

Страница 28: ...4B 93 93 39 1 2 450 900 Lbs 4648 Lbs A844L 93 93 39 1 2 450 900 Lbs 4648 Lbs A857B 93 93 39 1 2 450 900 Lbs 4648 Lbs A857L 93 93 39 1 2 450 900 Lbs 4648 Lbs A969L 93 130 39 1 2 800 1200 Lbs 7864 Lbs D...

Страница 29: ...2 425 850 Lbs 4390 Lbs CT 48 LT 48 84 84 39 1 2 425 850 Lbs 4390 Lbs CA 48 LA 48 93 93 39 1 2 450 900 Lbs 4648 Lbs CBA 48 LBA 48 93 93 39 1 2 450 900 Lbs 4648 Lbs CD 45 LD 45 93 93 39 1 2 450 900 Lbs...

Страница 30: ...e Series Model Width Length Depth Gallons Dry Weight Filled Weight VX 624B 76 84 34 325 730 Lbs 3437 Lbs VX 724L 84 84 32 425 800 Lbs 4340 Lbs VX 726B 84 84 39 1 2 425 800 Lbs 4340 Lbs VX 726L 84 84 3...

Страница 31: ...29...

Страница 32: ...LTR20081024 Rev B 6 12 08 L M S Customer Service Department 1462 East Ninth Street Pomona CA 91766 Toll Free 1 800 CAL SPAS Fax 1 909 629 3890 www calspas com...

Отзывы: