CONTROL SYSTEM 

 enables: 

Connection of the room thermostat*, S-C fan switch, two-* or three-way* valve and S-DS-MEC or  
S-DS-RMAG door contact*; 
* not a standard equipment - available as an option 
 
In this technical documentation we present the main connection diagrams air curtains SOLANO DESIGN with 
control S-C. The diagrams with the S-ECM external control module are available in the manual for the S-ECM. 
connection diagrams devices with S-SPLIT splitter are in documentation  
S-SPLIT. 

 

 
S-C

 - 3-speed fan switch with room thermostat  

Temperature range:: 
 

+10 … +30

o

Operating temperature range: 

0 … +40

o

IP/Insulation class:: IP30 
Max current: 
inductive 5A, resistive 6A 
Power supply: 230V/50Hz 

 

 
S-TOUCH 

Temperature range:: 
 

+5 … +35

o

Operating temperature range: -

10 … +60

o

IP/Insulation class: IP30 
Power supply: 24VDC 

 

 
S-V-2-

1/2”

  

 two-way 1/2 valve with 

actuator IP/Insulation class:  
IP20 Power supply: 
200 

 240V 50/60Hz  

Max water temperature: +93

o

Max water pressure: 2,1MPa 
Kvs: 3,0 m3/h 
Opening time: 18 s 

 

 
S-V-3-

1/2”

 

 three-way 1/2 valve  

with actuator  
IP/Insulation class: IP20  
Power supply: 
200 

 240V 50/60Hz  

Max water temperature: +93

o

Max water pressure: 2,1MPa 
Kvs: 3,4 m3/h 
Opening time: 18 s 

 

 
S-DS-RMAG

 

 magnetic door switch with relay 

Operating temperature range:  
-5 - +60

o

IP/Insulation class: IP 64 
Connectors: NO 
Max current: inductive/resistive 0,5A 
Max relay current: inductive 3A 
Max operating contactors distance: 6 mm 

 

 
S-DS-MEC

 

 mechanical door switch 

Operating temperature range: -10 -+80

o

C  

IP/Insulation class:  
IP 65 Connectors: 1xNC i 1xNO  
Max current: resistive 4A 

 inductive 10A  

Max Power load: 300VAC or 250VDC 

CONTROL SYSTEM

Содержание SOLANO W-100

Страница 1: ...1 SOLANO DESIGN TECHNICAL DOCUMENTATION TECHNISCHE DOCUMENTATIE GEBRUIKSAANWIJZING NOTICE D UTILISATION DOKUMENTACJA TECHNICZNA MŰSZAKI LEÍRÁS ...

Страница 2: ...3 8 GUIDELINES FOR CONNECTION WITH PIPELINE 13 9 OPERATION 13 10 CLEANING AND CONSERVATION 14 11 HEATING CAPACITY 67 Air Curtain SOLANO DESIGN is dedicated to install over the door opening it provides dynamic barrier cutting out external environment from indoor SOLANO DESIGN types DESIGN W 100 curtain with water heat exchanger max range 5 m DESIGN N 100 without heat exchanger ambient max range 5 m...

Страница 3: ...00 E 200 230 50 3x400 50 230 50 3x400 50 230 50 3x400 50 0 36 0 4 7 5 0 46 0 48 11 5 0 53 0 54 15 5 1 7 1 9 11 2 1 2 2 16 6 2 3 2 4 22 4 IP Insulation class 21 F Connecting stub 1 2 1 2 1 2 Max water temperature O C 95 95 95 1 6 1 6 1 6 Temperature increase T ºC 14 10 16 11 17 11 Weight kg 25 8 24 28 0 32 9 30 7 34 9 39 2 36 3 41 9 Weight of unit filled with water kg 26 6 34 2 40 8 ...

Страница 4: ... DESIGN E 200 ATTENTION When installing the unit as in the figure above a space 10 mm recommended between the bracket and the casing of curtain should be ensured contact between the bracket and the casing is forbidden It is recommended to level the unit so that all of the screws were equally burdened by the curtain In case of installation under the ceiling 4 pcs of M8 rods should be screwed into t...

Страница 5: ...ch bracket to the wall by two screws min M8 Installation of each bracket on the unit should also be performed using the supplied M8 rods as indicated in the figure below Type of curtain Distance mm DESIGN W 100 DESIGN E 100 DESIGN N 100 851 DESIGN W 150 DESIGN E 150 DESIGN N 150 1287 DESIGN W 200 DESIGN E 200 DESIGN N 200 1701 STAGES OF INSTALLATION BRACKETS ...

Страница 6: ...ange 5 35o C Operating temperature range 10 60o C IP Insulation class IP30 Power supply 24VDC S V 2 1 2 two way 1 2 valve with actuator IP Insulation class IP20 Power supply 200 240V 50 60Hz Max water temperature 93o C Max water pressure 2 1MPa Kvs 3 0 m3 h Opening time 18 s S V 3 1 2 three way 1 2 valve with actuator IP Insulation class IP20 Power supply 200 240V 50 60Hz Max water temperature 93o...

Страница 7: ... to the SOLANO DESIGN curtain the front panel must be opened by unscrewing the screws located in the upper parts of the unit Power and control wires must be routed through rubber passages located in the upper part of the air curtian CONNECTING GUIDE ...

Страница 8: ...mostat signal HEAT heating mode FAN room thermostat deactivated COOL cooling mode Œ Power supply 3x400V 50Hz DESIGN E 100 5x2 5 mm DESIGN E 150 5x2 5 mm DESIGN E 200 5x4 0 mm Max diameter of power supply wire 6 0 mm2 Ž Door contact S DS RMAG S DS MEC door closed opened contacts door opened closed contats Use DC jumper between connectors NC and NC if door contact not used OMY 2x1 0 mm2 Air curtain ...

Страница 9: ... supply B Return pipe water supply Ž Door contact S DS RMAG S DS MEC door closed opened contacts door opened closed contats Use DC jumper between connectors NC and 1 if door contact not used Air curtain step switch with thermostat S C OMY 5x1 0 mm2 FAN AUTO fan operating depending on room thermostat signal FAN CONT fan operating continously deactivated thermostat signal HEAT heating mode FAN room ...

Страница 10: ... connection S TOUCH connectors MASTER SLAVE connectors PT 1000 connectors LED INDICATORS G1 G2 G3 signalize number of fan speed operating S1 S2 S3 signalize number of set fan speed T signalize of valve set DC signalize of door contact set OPEN CLOSE signalize valve actuator WORK signalize of software working SW3 operating mode switch default settings SOLANO DESIGN CONTROL SYSTEM ...

Страница 11: ...Operating w o thermostat Werking zonder thermostaat Travail sans thermostat chauff age forcé Praca bez termostatu wymuszenie grzania termosztát nélküli K1 programme Signal from door switch or thermostat is main signal for the device to run K2 programme Signal from door switch is main signal for the device to run and thermostat is in charge of valve heaters Œ Power supply 230V 50Hz OMY 3x1mm2 S TOU...

Страница 12: ...ened contacts closed OMY 2x0 5mm2 EASY E ATTENTION Switch 4 on SW3 to the position E and then restart the system switching it off for 5 seconds Each time the device is switched off the heaters are being cooled for next 30 seconds Sample of door contact installation S DS MEC in cafe of installation in way which is show on drawing below connectors 21 and 22 need to be used DOOR CONTACT INSTALLATION ...

Страница 13: ... of the heating medium pressure above the permissible value 1 6 MPa While screwing exchanger to pipeline connecting stubs has to be hold by wrench The device is designed for operation inside buildings at temperatures above 0oC In low temperatures below 0ºC there is a danger of freezing of the medium The manufacturer bears no responsibility for damage of the heat exchanger resulting from freezing o...

Страница 14: ...and the adverse impact on fan operation causes waving If cleaning of heat exchanger is needed use listed guidelines Disconnect power supply of unit Dismount inlet grill guard It is recommended to use pressured air to clean the exchanger air stream need to be directed perpendicular to exchanger and moved along lamellas Other installed equipment do not need be cleaned CLEANING AND CONSERVATION ...

Отзывы: