Cairox CVA M Series Скачать руководство пользователя страница 13

 
 

p. 13

/

15

  User Instruction 

CAIROX 

     rev1 

 28/01/2022     

 

 

  

DESCRIPTION OF OPERATING CVA MPX … (PTC…PS) *

 

 

Electrical duct heaters CVA MPX 

 

(PTC…PS)

 are designed for the heaters power 

(0…100)

 % control by 

analog signal input 

(0…10)

 VDC, with integrated PTC (air velocity) and PS (air pressure) sensors.

 

When the heater power supply is switched on, controller (EKR-

K…)

 is in preparation mode for 30 seconds, LED 

ashes once every 5 seconds. If air velocity is detected by PTC sensor (rapid LED 1 

ashes when Min. 1,5 m/s is 

detected) and air pressure is greater than min 20kPA after preparation mode ends, LED 1 will start to flash once

 

every second and controller will initiate the heating based on demand, LED 2 is indicating when heating is initiated. 
If there is no air velocity detected and or there is not enough pressure in the duct, controller will not initiate the 
heating until air velocity and or pressure is detected.

 

Pre-heater casing and air duct before pre-heater should be insulated with rock wool 10cm (R~2,4m²K/W).

 

Depending on the mounting position of the heater in the duct relative to the motor (pre- or post-motor), the 

pressure hose must be placed on the "-" or "+" pipe, respectively.

 

*

 

- non standard option. For more information please contact us : www.cairox.com

 

  

DESCRIPTION OF OPERATING CVA MPI … 2NTC*

 

 

Electrical duct heaters CVA MPI 

 2NTC are designed with integrated temperature control, two 

temperature sensors, potentiometer on the top of the heater casing for temperature setpoint.

 

When the heater power supply is switched on, LED 6 on the controller (EKR-

K…) PCB 

(see Fig. 1 on page 4) 

ashes depending on the operating mode. If controller turns on the heating depending on the demand, LED 5 lights 

(see Fig. 1 on page 4)

.

 

Heaters CVA MPE 

 2NTC can operate in two modes:

 

1.

 

Control by the supply air temperature sensor (TJ-K10K), when the first (1) switch of JP1 -(R37) 

(see Fig. 1 on 

page 4) 

is in position ON. LED 6 

ashes twice per second. Set point temperature 

(0…30)

 °C.

 

2.

 

Control by the supply (TJ-K10K) and by the room (NTC10) air temperature sensor, when the first (1) switch of 

JP1 - (R37) 

(see Fig. 1 on page 4) 

is in position OFF. LED 6 

ashes once per second. Setpoint temperature 

(15…30)

 °C. 

In this mode is preprogrammed the minimum (15°C) and the maximum (45°C) temperatures of supply air. The room 
air temperature sensor is mounted in the wired remote control panel TR5K NTC10.

 

Depending on the operating mode there can be set the 

different

 desired (setpoint) air temperature by wired 

remote control panel TR5K NTC10.

 

*

 

- non standart option. Fore more information please contact us : www.cairox.com

 

 

  

DESCRIPTION OF OPERATING CVA MPE … 2NTC*

 

 

Electrical duct heaters CVA MPE 

… 2NTC are designed with integrated temperature control, two temperature

 

sensors, wired remote control panel (TR5K NTC10) for temperature setpoint.

 

When the heater power supply is switched on, LED 6 on the controller (EKR-

K…) PCB 

(see Fig. 1 on page 4) 

ashes depending on the operating mode. If controller turns on the heating depending on the demand, LED 5 lights 

(see Fig. 1 on page 4).

 

Heaters CVA MPE 

 2NTC can operate in two modes:

 

1.

 

Control by the supply air temperature sensor (TJ-K10K), when the first (1) switch of JP1 -(R37) 

(see Fig. 1 on 

page 4) 

is in position ON. LED 6 

ashes twice per second. Set point temperature 

(0…30)

 °C.

 

IMPORTANT: 

If  failure  appears,  power  supply  must  be  switched 

off

  and  only  then  performed  fault 

elimination works.

 

IMPORTANT: 

If  failure  appears,  power  supply  must  be  switched 

off

  and  only  then  performed  fault 

elimination works.

 

Содержание CVA M Series

Страница 1: ...p 1 15 User Instruction CAIROX rev1 28 01 2022 www cairox com USER INSTRUCTIONS ELECTRICAL CIRCULAR DUCT HEATERS CVA M CVA MPE CVA MPX CVA MPI CVA MQIA CVA MQI...

Страница 2: ...r to prevent product damage and employees injuries Do not lift product by power supplycable connectionbox Avoidimpactsandimpactloads Until final installation store products in dry place with humidity...

Страница 3: ...ion of operating CVA MPI 11 Description of operating CVA MPE 11 Description of operating CVA MPX 12 Description of operating CVA MPI PTC PS 12 Description of operating CVA MPE PTC PS 12 Description of...

Страница 4: ...Heaters intended only for inside installation If heater is installed in such way that can be accidental contact with heating elements protective grill must be installed The air velocity in the duct o...

Страница 5: ...PORTANT The installation to the mains power supply may only be wired by a competent electrician The power supply cable must be selected in the ratio with power of the heater When installing these heat...

Страница 6: ...FF ON 6 24VDC isusedinCVAESKMtypeheater Fig 4 Fig 5 MountingexampleCVA MPI NI 2NTC TemperaturesetpointknobandTRNTC10areusedinCVA MPI2NTCheaterversion TR5KNTC10isusedinCVA MPE2NTCheaterversion Fig 5 Fi...

Страница 7: ...rol signal ON OFF ON 6 24VDC from AHU if possible is used in CVA ESKM type pre heater DIMENSIONS Fig 8 Type 1 Type 2 Type 3 Type 4 Type 1 Standard CVA heater dimensions Type 2 CVA heater with external...

Страница 8: ...kW 880 782 81 400 CVA 450 373 276 81 450 CVA 500 373 276 81 500 CVA 500 12kW 500 402 81 500 CVA 500 15kW 630 532 81 500 CVA 500 18kW 630 532 81 500 CVA 500 21kW 770 672 81 500 CVA 500 24kW 880 782 81...

Страница 9: ...1 0 1 2 2 400 1 0 9 0 1 0 1 5 3 400 3 0 9 0 1 0 1 5 CVA 500 12kW 500 1060 1 230 9 1 0 2 400 12 1 0 1 5 3 400 12 1 0 1 5 CVA 500 15kW 500 1060 1 230 12 1 0 2 400 15 1 0 1 5 3 400 15 1 0 1 5 CVA 500 18k...

Страница 10: ...t ESKM External wired remote PWM ON OFF ON 6 24 VDC signal for temperature control 1B Duct diameter mm 100 100 mm 160 160 mm 355 355 mm 450 450 mm 125 125 mm 200 200 mm 400 400 mm 500 500 mm 150 150 m...

Страница 11: ...wer supply is switched on LED 6 on the controller EKR K PCB see Fig 1 on page 4 ashes once every 8 seconds if setpoint is 0 C and every second if setpoint is higher than 0 C If controller turns on the...

Страница 12: ...rockwool10cm R 2 4m K W Depending on the mounting position of the heater in the duct relative to the motor pre or post motor the pressurehosemustbeplacedonthe or pipe respectively DESCRIPTION OF OPERA...

Страница 13: ...controller turns on the heating depending on the demand LED 5lights seeFig 1onpage4 HeatersCVA MPE 2NTCcanoperateintwomodes 1 Control by the supply air temperature sensor TJ K10K when the first 1 swi...

Страница 14: ...rammedtheminimum 15 C andthemaximum 40 C temperatures ofsupplyair Theroom airtemperaturesensorismountedinthewiredpanelTRNTC10 Depending on the operating mode there can be set the di erent desired setp...

Страница 15: ...or resistance it must be 10k at 25 C 2 Air ow sensor fault Check sensor resistance It must be 22 between X15 X16 and 10 between X15 X18 Sensor must be clear 3 When the heater power supply is switched...