Press and hold the orange button on the front to connect the wireless 
transmitter to the selected channel. The next screen briefly appears:

The wireless sensor is now linked to the selected channel.
The next screen appears:

Repeat these steps from point 3 for the next wireless sensors (power supply for 
next wireless sensor).

Once the last wireless sensor has been connected, press and hold the orange 
button on the front to return to normal operation. Press until the following 
screen appears and the module will return to normal operation.

Removing the wireless sensors from the system:
You can also disconnect wireless sensors from the module. Open the housing by 
removing the bottom cover. Briefly press the “Config button” and the following 
message appears on the LCD screen:

The AQUAVISION 2DETECT is now in configuration mode for the wireless 
sensors. Briefly press the orange button on the front panel and the following 
message appears:

Briefly press the orange button on the front panel to scroll to the wireless 
sensors that are to be disconnected.

Press and hold the orange button to disconnect the wireless sensor. The sensor 
is then removed from the AQUAVISION 2DETECT’s memory. 
Next, the following screen appears:

Press and hold the orange button again and the system returns to normal 
operation.

Connecting the optional 5 VDC shut-off valve:

In the event of a leak, this alarm module can automatically control a shut-off valve and stop the water supply in the 
supply pipe. Only Cadis supplied 5VDC shut-off valves can be fitted.

Connect the Red connecting wire of the valve to NO +

Connect the Green connecting wire of the valve to NC +

Connect the Black connecting wire of the valve to – (minus)

NOTE: A contact on the the shut-off valve indicates the valve’s position. When the valve is closed, there is a closed 
contact between the yellow and white connecting wire. If required, this contact may also be forwarded to the BMS 
system.

Only after all the cables are connected can the housing be closed and the power supply to the module 
switched on. Otherwise, there is the risk of damage to the module.

The module will operate immediately and normally after switching on the power. Any additional settings for 
sending the alarms can be modified retrospectively by the users in the web server of the module using a PC 
or a laptop.

Содержание AQUAVISION 2DETECT

Страница 1: ...ate wired leak circuits can be connected to this module The maximum connection per circuit is 150 metres of leak detection cable or 10 leak detection probes Optionally an additional 8 wireless water l...

Страница 2: ...ng on This module has an integrated web server When correctly connected the module is accessible to each computer on the network ATTENTION Note the colour of the cables to the terminals G Green R Red...

Страница 3: ...t are to be disconnected Press and hold the orange button to disconnect the wireless sensor The sensor is then removed from the AQUAVISION 2DETECT s memory Next the following screen appears Press and...

Страница 4: ...l reset automatically CABLE BREAKAGE When a problem or breakage in the detection cable occurs the following message is displayed on the LCD This alarm will automatically reset as soon as the detection...

Страница 5: ...enter the following address in the command bar http 10 0 0 1 The login screen appears 2 Via wired connection with a network cable Connect a network cable between the AQUAVISION 2DETECT and the comput...

Страница 6: ...ce value in ohms of the Red Green detection loop Alarm timestamp this is the time that an alarm is activated The status of each wireless sensor is displayed The following statuses are possible No Leak...

Страница 7: ...e Alarm on a wireless sensor The Alarm History page All alarms that are activated in the AQUAVISION 2DETECT are stored in the memory together with a timestamp These alarms can be viewed at all times T...

Страница 8: ...used To retrieve the configured IP address press the button marked S_IP on the circuit board inside the housing The specified IP address is then displayed on the bottom line of the LCD screen SNMP if...

Страница 9: ...DF plan of the channel This plan is then loaded into the module and can be retrieved via the Home page Service level select the sensitivity for the detection cable Unit select the unit Metres or Feet...

Страница 10: ...Circuit 2 Leak location in meter Register 30011 Circuit 2 Leak Zone Register 30012 Circuit 2 Leakvalue in Register 30013 Wireless Sensor 1 Leak Status 0 No Leak 1 Leak Register 30014 Wireless Sensor...

Страница 11: ...uter of laptop with the AQUAVISION 2DETECT Adjust the IP address of the computer via Network Centre which you can access through the screen Configuration Click on Proporties Select Internet Protocol i...

Страница 12: ...type of device is no longer made it will be replaced by the newer release The warranty only applies to the equipment manufactured and supplied by the manufacturer All additional components that were i...

Отзывы: