20
Installation & Service Manual
The installer must use a specific vent starter
adapter at the flue collar connection,
supplied by the vent manufacturer to
adapt to its vent system. See Table 3F for
approved vent adapters. Discard CPVC
starter piece.
NOTICE
IMG00257
POLYPROPYLENE ADAPTER
W/ FLUE CLAMP
JOINT CONNECTOR REQUIRED
AT ALL COMPONENT CONNECTIONS
OF VENT SYSTEM
Figure 3-8 Near Boiler Polypropylene Venting Model 120
Model
Centrotherm InnoFlue SW
Duravent Polypro
Polypropylene Adapter/
Flue Clamp
Joint
Connector
Sidewall Retaining
Bracket*
Sidewall Adapter*
Polypropylene
Adapter
Joint
Connector
Sidewall Kit
40 - 100
ISAG0202 w/IAFC02
IANS02
IATP0202
ISTAGL0202
2PPS-AD
2PPS-LB
2PPS-HLK
120
ISAG0303 w/IAFC03
IANS03
IATP0303
ISTAGL0303
3PPS-AD
3PPS-LB
3PPS-HLK
* These parts are only needed if the alternate sidewall termination assembly is used.
Table 3F Approved PolypropyleneTerminations and Adapters
Polypropylene:
This product has been approved for use with polypropylene
vent with the manufacturers listed in Table 3E.
All terminations must comply with listed options in this manual
and be a single-wall vent offering.
For use of flex pipe, it is recommended to have the vent material
in 32°F or higher ambient space before bending at installation.
No bends should be made to greater than 45° and ONLY
installed in vertical or near vertical installations.
For support and special connections required, see the
manufacturer's instructions. All vent is to conform to standard
diameter and equivalent length requirements established.
When determining equivalent combustion air and vent length
for polypropylene flex piping:
•
1 foot of Duravent 3 inch flex is equivalent to 1.5 feet of
piping
•
1 foot of Duravent 4 inch flex is equivalent to 3 feet of
piping
•
1 foot of Centrotherm 3 inch flex is equivalent to 2 feet
of
piping
•
1 foot of Centrotherm 4 inch flex is equivalent to 2.75
feet
of
piping
When determining equivalent combustion air and vent length
for polypropylene single-wall piping:
•
1 foot of Duravent 4 inch single-wall pipe is equivalent
to 1.6 feet of piping
Use only the adapters and vent system listed
in Tables 3E and 3F. DO NOT mix vent
systems of different types or manufacturers,
unless listed in this manual. Failure to
comply could result in severe personal injury,
death, or substantial property damage.
WARNING
Installations must comply with applicable
national, state, and local codes. For
Canadian installation, polypropylene vent
must be listed as a ULC-S636 approved
system.
NOTICE
Installation of a polypropylene vent system
should adhere to the vent manufacturer’s
installation instructions supplied with the
vent system.
NOTICE
Table 3E Polypropylene Vent Pipe and Fittings
3
General
venting
Approved Polypropylene Vent Manufacturers
Make
Model
Centrotherm Eco Systems
InnoFlue SW/Flex
Duravent (M & G Group)
PolyPro Single-Wall / PolyPro
Flex
All vent connections MUST be secured by
the vent manufacturer's joint connector
(FIG. 3-8).
NOTICE
WARNING
Insulation should not be used on
polypropylene venting materials. The use
of insulation will cause increased vent wall
temperatures, which could result in vent