• Compare the read values with those on the table.
• Change power every 10 minutes and wait for it to stabilise.
• Access the user menu and, if necessary, change the parameters.
Fig. 69 - Cap removal
Fig. 70 - Digital pressure switch connection
DATA
P1
P2
P3
P4
P5
Stove depression -
temperature 8,5 kW 16 Pa - 140 °C
21 Pa - 160 °C
27 Pa - 175 °C
33 Pa - 190 °C
38 Pa - 210 °C
NB: for good combustion, the depression values must be between ± 5 Pa and the temperature values between ± 10°C.
7
SPECIAL MAINTENANCE
7.1
INTRODUCTION
For a long working life of the stove, have a periodic cleaning of the stove as described in the following paragrafs.
• Fume outlet pipes (fume c chimney flue + chimney pot) must always be cleaned, scrubbed and checked by an autho-
rized technician in compliance with local regulations, with the instructions of the manufacturer and those of your insurance
company.
• If there are no local regulations and no instruction from your insurance company, it is necessary to have your fume pipe, chim-
ney flue and chimney pot cleaned at least once a year.
• It is also necessary to have the combustion chamber, motors and fans cleaned and to have the gaskets and the electronical
elements checked at least once a year.
All these operations must be planned in time with your Autorized Technical Assistance Service.
• After a long ineffective time, before turning on the stove check if there are obstructions in the fume exhaust.
• If the stove had been using continuously and intensely, the whole system (chimney included), must be cleaned and checked
more frequently.
• In case of replacement of damaged pieces please ask for the original spare part at the Autorized Retailer.
7.2
FUME CONDUIT CLEANING
The exhaust system must be cleaned every 2/3 months.