EACIE Evacuation Alert Control and Indicating Equipment 

User Manual & Log Book 

 Approved Document No. DFU5030070 Rev 1 

 

Page 7 of 10 

 

4.2

 

EACIE Status Panel 

 

 

 
 

The status panel has a single pushbutton to silence the EACIE panel’s fault sounder and indicators to show 
system status information. 

 
 

Status Panel Pushbutton 

Status

 

Silence Fault Sounder 

Pressing this button silences the EACIE panel’s fault sounder. 
To resound, press this button again. 

 
 

Status Panel Indicators 

Status

 

What this means

 

What to do

 

Power 

Steady 

Green 

The EACIE panel is supplied with power 
(either mains or backup batteries). 

Power Fault 

Steady 

Yellow 

The EACIE panel has detected a fault with 
its power supply, batteries, or mains supply. 
The fault sounder will also activate (and 
may be silenced). 

The responsible 
person should call 
the service company. 

General Fault 

Flashing 

Yellow 

There is a fault condition on the system 
(excluding power faults). 
The fault sounder will also activate (and 
may be silenced). 

 

5  Glossary of Terms 

AL1:

 Access Level 1 (for the FRS). 

AL2: 

Access Level 2 (for authorised users). 

AL3: 

Access Level 3 (for authorised systems engineers). 

ARC: 

Alarm Receiving Centre. 

BS EN 54-2: 

Fire Detection and Fire Alarm Systems. Control and Indicating Equipment. 

BS EN 54-4:

 Fire Detection and Fire Alarm Systems. Power Supply Equipment. 

BS  8629:

  Evacuation  Systems  for  Fire  &  Rescue  Services.  Code  of  practice  for  the  design,  installation, 

commissioning  and  maintenance  of  evacuation  alert  systems  for  use  by  fire  and  rescue  services  in  buildings 
containing flats. 

EACIE:

 Evacuation Alert Control & Indicating Equipment. Component of an evacuation alert system through 

which evacuation alert devices (sounders) can be controlled, and that is used to monitor the correct functioning 
of the system and give audible and visible warning of any faults. 

EAS:

  Evacuation  Alert  System.  Comprises  of  evacuation  alert  devices,  sounder  controllers  and  an  EACIE 

panel with manual controls for the FRS to activate the evacuation alert devices. 

Evacuation Alert Device:

 Component of the evacuation alert system, not incorporated in the EACIE panel, 

which is used to signal to the occupants of a flat that evacuation is required by the FRS. These include sounders, 
visual alarm devices and tactile alert devices. 

Evacuation Alert Zone:

 May contain flats, part floors, or a complete floor of a building. 

FRS:

 Fire & Rescue Service. 

Responsible Person:

 Person responsible for supervising all matters pertaining to the evacuation alert system. 

 

 

Содержание EACIE

Страница 1: ...IE EVACUATION ALERT CONTROL AND INDICATING EQUIPMENT EACIE 1 to 4 Loop Panel User Manual Log Book Approved Document No DFU5030070 Rev 1 THE EACIE PANEL IS ONLY FOR USE BY THE FIRE AND RESCUE SERVICE F...

Страница 2: ...vacuation light turns red 2 Move switch UP to turn off the evacuation alert sounders The Evacuation light turns off EACIE Panel Switch Module Switch DOWN Sounders ON RED is lit Switch UP Sounders OFF...

Страница 3: ...sary of terms used in this document 1 IMPORTANT NOTES 4 2 INTRODUCTION 4 3 USER RESPONSIBILITIES 5 4 CONTROLS INDICATORS 6 4 1 EACIE FRONT PANEL 6 4 2 EACIE STATUS PANEL 7 5 GLOSSARY OF TERMS 7 6 SYST...

Страница 4: ...d interface the EACIE panel allows the FRS to operate evacuation alert devices located in residential flats Evacuation alert devices include sounders visual indicators and vibrating pillow pads In add...

Страница 5: ...operated and to contact the fire and rescue service if they are unable to evacuate The premises management should be advised to incorporate this advice within fire action notices for the building e e...

Страница 6: ...Switch Module Manual Controls Status What this means Evacuation toggle switch up to 48 off UP is OFF Deactivates evacuation alert sounders in the associated evacuation alert zone floor up to 48 off DO...

Страница 7: ...ng Centre BS EN 54 2 Fire Detection and Fire Alarm Systems Control and Indicating Equipment BS EN 54 4 Fire Detection and Fire Alarm Systems Power Supply Equipment BS 8629 Evacuation Systems for Fire...

Страница 8: ...S INSTALLED BY THE SYSTEM WAS COMMISSIONED BY THE SYSTEM WAS ACCEPTED BY FOR SERVICE DETAILS OF WHO YOU SHOULD CONTACT IF MAINTENANCE IS REQUIRED THE SYSTEM IS MAINTAINED UNDER CONTRACT BY Company ___...

Страница 9: ...Details of any non maintenance events should be recorded here e g use by the FRS and faults Note Before entering details on this form photocopy additional sheets for future use DATE TIME EVENT e g use...

Страница 10: ...Rev 1 Page 10 of 10 Details of any maintenance work should be recorded here Note Before entering details on this form photocopy additional sheets for future use DATE TIME EVACUATION ALERT ZONE DEVICE...

Отзывы: