CAST XFP ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Page 8 of 16
Commissioning/Programming Quick Start Guide
Approved Document No. DFU5020010 Rev 4
Option 2: Select ‘Erase Loop 1 device data first? Yes’
CAUTION: USING THIS OPTION WILL COMPLETELY ERASE THE PANEL’S DATABASE OF
STORED LOOP DEVICE INFORMATION EXCLUDING DEVICE ADDRESSES PREVIOUSLY
ASSIGNED BY A CAPROG PROGRAMMER, WHICH IS RETAINED. THIS IS DIFFERENT TO
THE AUTO ADDRESS FUNCTION. USE THIS OPTION WITH EXTREME CARE
.
Use this option if the panel has not previously been programmed, or if you want to program an existing system
as if it were a new system.
Press the scroll
▲
button to select ‘Yes’ then press the Accept
button shown below:
The following message will appear:
Only if you are confident to proceed, press the scroll
▲
button to select ‘Yes’, then press the Accept
button.
The panel will erase its database, update its flash memory and start a loop learn.
Wait for the process to complete and a summary window will appear, similar to the one shown below:
Press the Accept
button then press Escape
button x 3 to return the panel to a normal condition.
When requested by the panel remove the NVM link shown below:
AFTER A SUCCESSFUL LOOP LEARN
YOU WILL HAVE A ‘ONE OUT, ALL OUT’ FIRE ALARM SYSTEM.
See Table 1 (page 6) for the default device assignment following a loop learn.
Are you sure you want to erase
the Database? No
112 devices found
Auto learn complete, Press Accept