ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 26 of 48
CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
When requested by the panel remove the NVM link shown below:
Option 2: Select ‘Continue from last address? Yes’
Use this option if you do not want to erase the stored loop device data. The panel will start to learn the
loop from the last known address in its memory. Existing data will not be overwritten, e.g. zone and
group allocation, device names, etc., will remain unchanged. The only data that will be overwritten is
device type and whether or not it is fitted.
Press the scroll
5
button to select ‘Yes’ then press the Accept
4
button shown below:
The panel will perform an auto address. Wait for the process to complete and a brief summary window
will appear, similar to the one shown below:
Press the Accept
4
button then press the Escape
3
button x 4 to return the panel to a normal condition.
When requested by the panel remove the NVM link shown below:
6: 50
16 Jan : Normal
Remove the NVM Un-Lock link
Continue from last address? Yes
112 Devices Found
Auto learn complete, Press Accept
6: 50
16 Jan : Normal
Remove the NVM Un-Lock link
AFTER A SUCCESSFUL AUTO ADDRESS, YOU WILL HAVE A ‘ONE OUT, ALL OUT’ FIRE ALARM SYSTEM.
See Table 1, page 24 for the default device assignment following an auto address.
The panel will perform an auto address. Wait for the process to complete and a brief summary window
will appear, similar to the one shown below:
Press the Accept
4
button then press the Escape
3
button x 4 to return the panel to a normal condition.
112 Devices Found
Auto learn complete, Press Accept