Installation 

Absence detection

 

 

To use absence detection a retractive (momentary) switch must be connected between the 2 terminals on the 
diagram. Note that this will be switching mains voltage.  

 

The unit ships with presence detection as default. To change to absence detection, press and release the external 
switch 5 times within the first minute of power up. The LED will turn on solid for 30 seconds to indicate absence 
mode has been selected.  

 

To change back to presence detection, repeat the above procedure—the LED will flash for 30 seconds to indicate 
presence mode has been selected. 

Note: 

the above adjustments can also be made using the UHS5 or UNLCDHS handsets. See Programming sections. 

When power is applied to the unit, the load will turn on immediately. 
Set the timeout to 10 seconds, vacate the room or remain very still and wait for the load to switch off . 
Check that the load switches on when movement is detected. 
The unit is now ready for programming. 

Power-up test procedure 

Choosing a Suitable Location 

The detector should be sited so that the occupants of the room fall inside the detection pattern shown opposite). 

 

Avoid positioning the unit where direct sunlight may enter the sensor element.  

 

Do not site the sensor within 1m of any lighting, forced air heating or ventilation. 

 

Do not fix the sensor to an unstable or vibrating surface. 

 

Avoid metallic objects directly in front of the sensor head.  

The UNLCDHS has the ability to read back the settings stored in a device. 

To read back individual parameters 

 

Navigate to the parameter and press the ‘R’ (Read) button whilst pointing at the device. The handset will click 
when the parameter has been read back, the device will flash its LED, and the value will be shown against the 
parameter in the menu. 

To read back all of the parameters in a menu 

 

Press and hold the ‘R’ (Read) button for more than 1 second. 

 

The handset will click every time a parameter is received 

 

The device will show multiple flashes of its LED 

 

All of the values will be shown against the parameters in the menu. 

 

The individual parameters may be edited and then saved as a ‘Macro’. 

Notes 

 

If a parameter(s) has been missed because of a communication error, the missing value(s) is replaced by dashes. 

 

When reading back, the Channel 1 relay (where fitted) will temporarily be switched off, and will return to it’s 
normal state 2 seconds after the read back has been completed. 

Readback function 

(UNLCDHS handset only)

 

Содержание MWS3A-PRM

Страница 1: ...y programmable using an IR handset Features Front features Back features Ceiling microwave presence absence detector MWS3A PRM Product Guide Microwave Sensor Detects movement within the unit s detecti...

Страница 2: ...ed In either case sensitivity to movement of the microwave sensor can be adjusted using the Sensitivity parameter HINT To assist in setting the Sensitivity turn on the Walk Test LED which will flash r...

Страница 3: ...shown opposite Avoid positioning the unit where direct sunlight may enter the sensor element Do not site the sensor within 1m of any lighting forced air heating or ventilation Do not fix the sensor to...

Страница 4: ...efore affixing the cable clamp The clamp MUST clamp the outer sheath s only Bend cores as shown Wire stripping details 1 5 4 3 Hole 74mm Attach cable clamp Flush fixing Surface fixing Head locking 1 3...

Страница 5: ...nified by the Shift 1 and Shift 2 LEDs Number of Shift key presses The functionality of the MWS3A PRM is controlled by a number of parameters which can be changed or programmed by any of the following...

Страница 6: ...ess of ambient light level However if there is sufficient ambient light they will turn off again after the Lux Time Note that whenever the an external switch is pressed whether in absence or presence...

Страница 7: ...7 This page intentionally left blank...

Страница 8: ...tralia and all of Europe except UK France Portugal Germany Switzerland Austria Slovak Republic Republic of Ireland 10 525GHz R3 France Portugal Switzerland 9 900GHz R4 Germany Austria Slovak Republic...

Отзывы: