3.2 Technical Indicators
Environment temperature: 23±5°C, relative humidity
(RH):<75%
3.2.1 AC Current
Accuracy
Resolution
Measuring
range
4mA
40mA
400mA
0.001mA
0.01mA
0.1mA
- Maximum input current: 150A AC
- Frequency range: 40~1kHz
3.2.2 DC Voltage
Accuracy
Resolution
Measuring range
±(0.5% r digits)
4
4V
40V
600V
0.01V
0.1V
1V
0.001V
400V
- Input impedance: 10M
Ω
- Maximum input voltage: 600V DC or AC(RMS)
In the small voltage measuring range, the probe is not
connected with the circuit to be tested, and the meter
may have fluctuating readings, which is normal and
caused by the meter's high sensitivity. This does not
affect actual measurement results.
Note:
3.2.3 AC Voltage
Accuracy
Resolution
Measuring range
±(
% r digits)
1.0
3
4V
40V
600V
0.01V
0.1V
1V
0.001V
400V
- Input impedance: 10M
Ω
- Maximum input voltage: 600V DC or AC(RMS)
- Frequency range: 40~1kHz(sine wave)
In the small voltage measuring range, the probe is not
connected with the circuit to be tested, and the meter
may have fluctuating readings, which is normal and
caused by the meter's high sensitivity. This does not
affect actual measurement results.
Note:
3.2.4 Resistance
Accuracy
Resolution
Measuring range
400
Ω
0.1
Ω
4k
Ω
0.001k
Ω
40k
Ω
400k
Ω
4M
Ω
40M
Ω
0.01k
Ω
0.1k
Ω
0.001M
Ω
0.01M
Ω
±(
% r digits)
0.8
3
- Open circuit voltage: about 1.0V
- Overload protection: 600V DC or AC (RMS)
LPF(50Hz/60Hz)
Wide(40Hz~1kHz)
±(2.0% + )
10
±(3.0% + )
5
4A
40A
150A
0.001A
0.01A
0.1A
±(2.0% + )
5
±(2.0% + )
10
±(3.0% + )
3
±(3.0% + )
5
±(
% r digits)
1.0
3
33
34
Leakage Clamp Meter
Leakage Clamp Meter