Document:
Date
Created By:
LPN00855X0001A0_A
04-21-2021
TMT
INSTALLATION INSTRUCTIONS
C-WP-C-TR Series
http://lighting.cree.com/warranty | 1-800-236-6800
STEP 1:
Make the following electrical connections:
a. Connect the black luminaire lead labeled unswitched
hot to the unswitched voltage supply lead.
b. Connect the black luminaire lead labeled
switched hot to the switched supply lead.
c. Connect white luminaire lead to the neutral
supply lead (Hot 2 for 208/240V wiring).
d. Connect ground bare or green wire lead
to the supply ground lead.
STEP 2:
Turn on unswitched voltage supply to luminaire. Keep the switched
voltage supply to luminaire off.
STEP 3:
Connect the battery female connector to the male connector on the
emergency driver.
WHITE
SUPPL
Y WIRING
LUMINAIRE
GROUND
BARE OR
GREEN
BLACK SWITCHED
SWITCHED HOT
BLACK
UNSWITCHED
UNSWITCHED HOT
WHITE
NEUTRAL
OR HOT 2
*** MALE CONNECTOR
EB DRIVER
*** FEMALE CONNECTOR
EB BATTERY
*** NOTE:
Do NOT mate male connector from the
emergency driver to the female connector from
the battery until AC power is supplied to unswitched
hot lead to luminaire
ELECTRICAL CONNECTIONS- LUMINIARE WITH EMERGENCY DRIVER