B-Box Residential installation guidance
36
/
43
Appendix 1
SMA charger min capacity
Parameter setup for B-Box2.5
Charging the battery Usage through battery backup system without increased self-consumption
Parameters
Setup value
003.07Batt Typ
Li Lon_Ext-BMS
003.10Batt Cpynom
50
262.01ProtResSOC
3
262.02BatResSOC
10
Charging the battery usage through battery backup system with increased self-consumption
Parameters
Setup value
003.07Batt Typ
Li Lon_Ext-BMS
003.10Batt Cpynom
50
261.01SlfCsmplncEna
Enable
261.03Saisonenable
Yes
262.01ProtResSOC
3
262.02BatResSOC
6
262.03BUResSOC
0
262.04PVResSOC
8
262.05MinSlfCsmpSOC
75
Charging the battery usage through system for increased self-consumption without a battery backup grid
Parameters
Setup value
003.07Batt Typ
Li Lon_Ext-BMS
003.10Batt Cpynom
50
261.01SlfCsmplncEna
Enable
261.03Saisonenable
Yes
262.01ProtResSOC
3
262.02BatResSOC
6
Содержание B-BOX 10.0
Страница 20: ...B Box Residential installation guidance 20 43 7 2Grounded cable connection between several B Box ...
Страница 21: ...B Box Residential installation guidance 21 43 7 3Power cable connection between several B Box ...
Страница 43: ...B Box Residential installation guidance 43 43 B Box 7 5 15 B Box 10 0 10 B Box 12 8 10 ...