Operating range: outdoor ambient air temperature between -7°C and +43°C.  
Performance levels are maximised b15°C and +25°C. The machine is not guaranteed to run properly 
outside the -7°C / +43°C operating range. 
Water resistance index for electrical parts : IPX4. 

Set point temperature regulation range: 

• 

Heating mode: 18°C to 35°C 

• 

Cooling mode: 12°C to 30°C 

 

Technical data 

IPHCR 

15 

IPHCR 

20 

IPHCR 

26 

IPHCR 

33 

IPHCR 

40 

IPHCR 

45 

IPHCR 

55 

IPHCR 

70 

IPHCR 

70T 

IPHCR 

100T 

Advised water volume 

(m3) 

15~30 

20~40 

25~45 

30~55 

35~65 

40~75 

50~95 

65~120 

65~120 

90~160 

Power supply 

230 V / 1 phase / ~ 50 Hz 60Hz 

400 V / 3 ph /  

~50 Hz 60Hz 

max/min consumed 
power(kW)* 

1,06/ 

0,13 

1,2/ 

0,17 

1,5/ 

0,19 

1,81/ 

0,23 

2,2/ 

0,27 

2,6/ 

0,30 

3,18/ 

0,36 

3,8/ 

0,55 

3,9/ 

0,55 

5,2/ 

0,61 

max/min consumed 

current  (A)* 

4,60/ 

0,56 

5,2/ 

0,74 

6,5/ 

0,83 

7,87/ 

1,00 

9,6/ 

1,17 

11,3/ 

1,3 

13,8/ 

1,57 

16,5/ 

2,4 

5,6/ 

0,79 

7,4/ 

0,88 

Maximum inlet 

current(A) 

6,5 

8,0 

9,0 

11,5 

12,0 

13,0 

17,0 

20,0 

7,0 

9,5 

Recommended flowrate 

(m3/h) 

2 to 4 

2 to 4 

3 to 4 

4 to 6 

5 to 7 

6,5 to 8,5  8 to 10 

10 to 12 

10 to 12 

12 to 18 

Ext. Diam. of hydraulic 
pipe 

50 mm 

Net weight kg 

42 

45 

49 

50 

52 

63 

68 

90 

93 

120 

Dim (length x width x 
height) mm 

894 x 359 x 648 

954 x 359 x 648 

954x429 

x 648 

954x429

x 755 

1084 x 429 x 948 

1154 x 

539 x 948 

Sound power level dB(A) 
at max / middle / min. 
speeds** 

61/ 

53,9/ 

51,6 

62/ 

55,2/ 

52,6 

63,7/ 
57,1/ 

52,4 

64,5/ 
59,5/ 

55,9 

68,8/ 
60,3/ 

55,1 

67,6/ 
60,3/ 

56,9 

69/ 

61,2/ 

55,7 

69,7/ 
63,2/ 

58,3 

69,7/ 
63,2/ 

58,3 

69,5/ 
60,6/ 

57,4 

Refrigerant mass 
R 32 (grams) 

550 

650 

750 

800 

950 

1000 

1200 

2100 

2100 

2400 

Standardised heating performance data according to the standard AFNOR AC-P 90-327 (ex DTP n°10): air temperature 15°C. water 
temperature 26°C. relative humidity 70 %

 

Heating power at max 
speed (kW) 

4,8 

6,3  

7,3  

8,7  

10,5  

11,5  

14,0  

18,0  

18,0  

24,5  

COP at  
max / 

50 %

 / min speeds 

4,5/6,3/

7,3 

5,0/6,6/

7,4 

4,8/6,8/

7,7 

4,8/6,8/

7,7 

4,6/6,6/

7,8 

4,5/6,4/

7,8 

4,4/6,3/

7,7 

4,8/6,8/

8,1 

4,8/6,8/ 

8,1 

4,7/7,0/ 

8,0 

Heating performance data. air temperature 26°C. water temperature 26°C. relative humidity 80 % 

Heating power at max 
speed (kW) 

6,5 

8,5  

10,5  

13,0  

15,0  

17,5  

20,5  

27,5  

27,3  

35,8  

COP at  
max / 

50 %

 / min speeds 

6,0/10,5

/14,7 

7,4/10,9

/14,8 

7,4/11,0

/15,0  

7,3/11,0

/15,4  

6,7/10,9

/15,5  

6,2/11,1

/15,8 

6,0/10,7

/15,3  

6,5/11,2

/15,4  

6,5/11,2

/15,3  

5,8/10,9 

/15,6  

Cooling performance data. air temperature 35°C. water temperature 28°C. relative humidity 80 % 

Cooling power (kW)  at 
max speed 

3,0

 

4,0 

4,6 

5,6 

6,8 

7,8 

10,0 

12,2 

12,2 

16,5 

*air 15°C, water 26°C   

 

**according to EN 12102 and EN ISO 3744 

Содержание Fairland IPHCR100T

Страница 1: ...1 18 2018 12 B Code 33315 BWT FAIRLAND INVERTER PLUS Pompe chaleur IPHCR15 IPHCR20 IPHCR26 IPHCR33 IPHCR40 IPHCR45 IPHCR55 IPHCR70 IPHCR70T IPHCR100T...

Страница 2: ...nsions 24 V Product installation 25 V 1 Siting 25 V 2 Support 26 V 3 Handling 26 V 4 Connection to the hydraulic circuit 26 V 5 Wiring 27 V 6 Heating priority 28 VI Start up and operation 28 VII Upkee...

Страница 3: ...d after installation 1 Use a It must be installed or removed by professionals and it is forbidden to dismantle and refit without permission b Don t put obstacles before the air inlet and outlet of the...

Страница 4: ...far away from any source of fire d Storage place must be bright wide open and good ventilation ventilation equipment is required 4 Maintenance Notice a If maintenance or scrap is required contact a qu...

Страница 5: ...s cheaper than other conventional heating means Unlike On Off heat pumps Inverter heat pumps can modulate their operating mode and adapt it to the swimming pool s heating demand This characteristic ma...

Страница 6: ...3 68 90 93 120 Dim length x width x height mm 894 x 359 x 648 954 x 359 x 648 954x429 x 648 954x429 x 755 1084 x 429 x 948 1154 x 539 x 948 Sound power level dB A at max middle min speeds 61 53 9 51 6...

Страница 7: ...he machine will revert to normal operating mode The heat pump is fitted with a flow controller that only allows the machine to start up when the water flow rate through the machine is adequate see the...

Страница 8: ...reated against corrosion Piping must be attached to the wall to be supported but not by the machine Make sure the filtration pump can overcome the height difference between the filtration pump and the...

Страница 9: ...A max bipolar trtrapolar Power cable wire cross section in mm2 3 x 1 5 3 x 1 5 3 x 2 5 3 x 2 5 3 x 2 5 3 x 2 5 3 x 4 0 3 x 6 0 5 x 2 5 5 x 2 5 Remote installed control panel cable wire cross section i...

Страница 10: ...nds to access the parameter modification menu The P0 parameter followed by 0 is displayed on the screen P0 0 Press to modify P0 then press to scroll until 1 is displayed P0 1 Press once again to confi...

Страница 11: ...it shuts off still lit VI 2 Selecting the operating function There are three operating functions available heating cooling auto If the auto function is active the machine will automatically go into he...

Страница 12: ...timately selected by the operator will be active when restarting the heat pump after being off VI 3 Selecting the set temperature value Screen being unlocked press or to display the set temperature an...

Страница 13: ...he caps provided to avoid any unwanted guests taking up residence over the winter period Cover the machine if possible to prevent dirt from building up on the external parts VII 2 Technical inspection...

Страница 14: ...at cooling mode 7 P0 Controller communication failure 8 P1 Water inlet temp sensor failure 9 P2 Water outlet temp sensor failure 10 P3 Gas exhaust temp sensor failure 11 P4 Evaporator coil pipe temp s...

Страница 15: ...coolness of ambient air Inadequate programming of the timer that controls filtration start and stop Length of the filtration cycel too short Filtration only at night when the ambient T C is particula...

Страница 16: ...16 18 2018 12 B Code 33315 NOTES...

Страница 17: ...17 18 2018 12 B Code 33315...

Страница 18: ...18 18 2018 12 B Code 33315 Version B18Ir32...

Отзывы: