V.6) Heating priority :  

It is possible to set the system up so that the heat pump will start up filtration outside programmed 
filtration cycles if a heating demand is detected. This allows the pool water temperature to be held more 
constantly around the set point. 
In this case, the heat pump will start the filtration up every our (unless it is already running) to measure 
the pool water temperature. If a heating demand is detected, it keeps the filtration pump running, 
otherwise it stops the filtration pump after 3 minutes. 
To do this, the electrical connections to be made will use the terminals marked P1 and P2 on the heat 
pump terminal block: 
 

 

 

 

 

 

 

 

 

 

 

 

 

Next, activate heating priority as follows on the control panel: 

 

Press the   and  

 icons simultaneously for 5 seconds to access the parameter modification menu. 

 

The “P0” parameter followed by “0” is displayed on the screen: “P0  0”. 

 

Press   to modify P0,  then press 

 to scroll until 1 is displayed : “P0 1” 

 

Press   once again to confirm, 

 

Press   to exit the parameter modification menu. 

To leave the heating priority mode, set the P0 parameter back to 

0

 following the above procedure. 

IMPORTANT : do not modify the value of parameters other than P0 

VI.

 

Start up and operation   

 

 

 

 

 

 

 

 

After verifying that there is an adequate flow rate through the machine, press the 

start (and stop) icon 

 for 3 seconds to activate the screen, then press on 

 to 

start the heat pump. Where the machine detects the need to heat the water, in the 
following 3 minutes, the fan sill start, followed by the compressor after about 30 
seconds.  

 

 
 
 
 
 

~ 230 V, 50 Hz 60 Hz 

DDR 30 mA 

Thermal magnetic circuit 

breaker 

Filtration pump 

Switch 

co

il 

Power 

contacts  

Thermal magnetic circuit breaker 

~ 230 V (mono) ou 400 V 
(tri) , 50 Hz 60 Hz 

Filtration 
timer 

L  N  Earth 

P1 

P2 

Heat pump 

Содержание Fairland IPHCR100T

Страница 1: ...1 18 2018 12 B Code 33315 BWT FAIRLAND INVERTER PLUS Pompe chaleur IPHCR15 IPHCR20 IPHCR26 IPHCR33 IPHCR40 IPHCR45 IPHCR55 IPHCR70 IPHCR70T IPHCR100T...

Страница 2: ...nsions 24 V Product installation 25 V 1 Siting 25 V 2 Support 26 V 3 Handling 26 V 4 Connection to the hydraulic circuit 26 V 5 Wiring 27 V 6 Heating priority 28 VI Start up and operation 28 VII Upkee...

Страница 3: ...d after installation 1 Use a It must be installed or removed by professionals and it is forbidden to dismantle and refit without permission b Don t put obstacles before the air inlet and outlet of the...

Страница 4: ...far away from any source of fire d Storage place must be bright wide open and good ventilation ventilation equipment is required 4 Maintenance Notice a If maintenance or scrap is required contact a qu...

Страница 5: ...s cheaper than other conventional heating means Unlike On Off heat pumps Inverter heat pumps can modulate their operating mode and adapt it to the swimming pool s heating demand This characteristic ma...

Страница 6: ...3 68 90 93 120 Dim length x width x height mm 894 x 359 x 648 954 x 359 x 648 954x429 x 648 954x429 x 755 1084 x 429 x 948 1154 x 539 x 948 Sound power level dB A at max middle min speeds 61 53 9 51 6...

Страница 7: ...he machine will revert to normal operating mode The heat pump is fitted with a flow controller that only allows the machine to start up when the water flow rate through the machine is adequate see the...

Страница 8: ...reated against corrosion Piping must be attached to the wall to be supported but not by the machine Make sure the filtration pump can overcome the height difference between the filtration pump and the...

Страница 9: ...A max bipolar trtrapolar Power cable wire cross section in mm2 3 x 1 5 3 x 1 5 3 x 2 5 3 x 2 5 3 x 2 5 3 x 2 5 3 x 4 0 3 x 6 0 5 x 2 5 5 x 2 5 Remote installed control panel cable wire cross section i...

Страница 10: ...nds to access the parameter modification menu The P0 parameter followed by 0 is displayed on the screen P0 0 Press to modify P0 then press to scroll until 1 is displayed P0 1 Press once again to confi...

Страница 11: ...it shuts off still lit VI 2 Selecting the operating function There are three operating functions available heating cooling auto If the auto function is active the machine will automatically go into he...

Страница 12: ...timately selected by the operator will be active when restarting the heat pump after being off VI 3 Selecting the set temperature value Screen being unlocked press or to display the set temperature an...

Страница 13: ...he caps provided to avoid any unwanted guests taking up residence over the winter period Cover the machine if possible to prevent dirt from building up on the external parts VII 2 Technical inspection...

Страница 14: ...at cooling mode 7 P0 Controller communication failure 8 P1 Water inlet temp sensor failure 9 P2 Water outlet temp sensor failure 10 P3 Gas exhaust temp sensor failure 11 P4 Evaporator coil pipe temp s...

Страница 15: ...coolness of ambient air Inadequate programming of the timer that controls filtration start and stop Length of the filtration cycel too short Filtration only at night when the ambient T C is particula...

Страница 16: ...16 18 2018 12 B Code 33315 NOTES...

Страница 17: ...17 18 2018 12 B Code 33315...

Страница 18: ...18 18 2018 12 B Code 33315 Version B18Ir32...

Отзывы: