V.6) Heating priority :
It is possible to set the system up so that the heat pump will start up filtration outside programmed
filtration cycles if a heating demand is detected. This allows the pool water temperature to be held more
constantly around the set point.
In this case, the heat pump will start the filtration up every our (unless it is already running) to measure
the pool water temperature. If a heating demand is detected, it keeps the filtration pump running,
otherwise it stops the filtration pump after 3 minutes.
To do this, the electrical connections to be made will use the terminals marked P1 and P2 on the heat
pump terminal block:
Next, activate heating priority as follows on the control panel:
Press the and
icons simultaneously for 5 seconds to access the parameter modification menu.
The “P0” parameter followed by “0” is displayed on the screen: “P0 0”.
Press to modify P0, then press
to scroll until 1 is displayed : “P0 1”
Press once again to confirm,
Press to exit the parameter modification menu.
To leave the heating priority mode, set the P0 parameter back to
0
following the above procedure.
!
IMPORTANT : do not modify the value of parameters other than P0
VI.
Start up and operation
After verifying that there is an adequate flow rate through the machine, press the
start (and stop) icon
for 3 seconds to activate the screen, then press on
to
start the heat pump. Where the machine detects the need to heat the water, in the
following 3 minutes, the fan sill start, followed by the compressor after about 30
seconds.
~ 230 V, 50 Hz 60 Hz
DDR 30 mA
Thermal magnetic circuit
breaker
Filtration pump
Switch
co
il
Power
contacts
Thermal magnetic circuit breaker
~ 230 V (mono) ou 400 V
(tri) , 50 Hz 60 Hz
Filtration
timer
L N Earth
P1
P2
Heat pump