5 | Installation
12 / 36
0870201428_RA0165-0305D_O2_-0004_IM_en
5.2.3 Cooling Water Connection (Optional)
Water-oil heat exchanger without inlet accessories
WHE
CWO
CWI
CWO
TV
PS
WBV
WF
CWI
WHE
Water-oil heat exchanger with inlet accessories
CWI
Cooling water inlet
PS
Pressure switch
CWO
Cooling water outlet
WBV
Water bypass valve
WHE
Water-oil heat exchanger
WF
Water filter
TV
Thermostatic valve
The thermostatic valve (TV) is used to control the water flow in order to keep a stable
machine temperature.
The pressure switch (PS) is used to monitor the presence of water at the cooling system
of the machine.
When the pressure switch detects a pressure lower than 2 bar, the machine must be
stopped.
The water bypass valve (WBV) is used at the first machine start-up. At that moment it
should be open (approx. 90 seconds) to prime the water heat exchanger, afterwards it
should be closed.
• Connect the cooling water connections (CWI / CWO) to the water supply.
Connection size:
• If necessary, electrically connect the pressure switch (PS), see
sure Switch of Water-oil Heat Exchanger (Optional) [
• Make sure that the cooling water complies with the following requirements:
Min. supply capacity
l/min
2.5
Water pressure
bar
2 ... 6
Supply temperature
°C
+5 ... +35
Required pressure differential across supply
and return
bar
≥
1