Commissioning | 6
0870168572_MV0310B_-0001_IM_en_MD
17 / 32
6.1.2 DIP-Switch
DIP-Switch
Description
Standard
AI1
C = Analogue input 1 operates in current mode (2 … 20 mA)
0 = Analogue input 1 located in test mode
V = Analogue input 1 operates in voltage mode (2 … 10 V)
V
AI2
C = Analogue input 2 operates in current mode (2 … 20 mA)
0 = Analogue input 2 located in test mode
V = Analogue input 2 operates in voltage mode (2 … 10 V)
C
AO1
C = Analogue output operates in current mode (2 … 20 mA)
0 = Analogue output located in test mode
V = Analogue output operates in voltage mode (2 … 10 V)
C
DI
0 = Digital input is isolated by grounding
1 = Common grounding of digital input is connected to 24 V
2 = Common grounding of digital input is connected to ground
2
RS 485
0 = Connection resistance 120 Ohm is connected
1 = Pull-Up and Pull-Down resistance of 10k Ohm for bias
voltage is connected
2 = No timing settings and no bias voltage resistance are
connected
2