5 | Installation
12 / 32
0870168572_MV0310B_-0001_IM_en_MD
Double star connection, multi-voltage
motor with 9 pins (low voltage):
Star connection, multi-voltage motor
with 9 pins (high voltage):
5.4.2 Wiring Diagram Variable-Frequency Drive
CAUTION
The machine can start immediately when power is supplied.
Risk of inadvertent start-up!
• Make sure that a start-up will not lead to a dangerous situation.
1
2
3
L1
L2
L3
PE
PE2
The leakage current exceeds 3.5 mA. According to EN 61800-5-1 an additional pro-
tective earth conductor (PE2) must be provided:
• Connect the additional protective earth conductor (PE2). Use at least the same
cross section as for PE.